15-16-460  Dry pipe systems.
   A dry pipe system shall be permitted only where heat is not adequate to prevent freezing of water in all or sections of a system. If the sprinklers in such unheated spaces are 25 percent or less of the total number of sprinklers required on a system having a total of 100 or more sprinklers, only such 25 percent or less shall be on the dry system and the remainder shall be on the wet system.
   The dry pipe system shall be isolated from the water supplies (or from the wet portion of the system, if a combined wet and dry pipe system) by a dry pipe valve located at an accessible point as near as practicable to the dry system, adequately protected against mechanical injury and freezing.
(Prior code §  91-30; Amend Coun. J. 10-30-96, p. 31216, § 1)