Skip to code content (skip section selection)
Compare to:

You are viewing an archived code

15-16-500  Gauges.
   There shall be provided dial spring pressure gauges in each sprinkler system on the riser above and below the alarm valve if so equipped, at the system main drain; at each main drain associated with a floor control valve; at the pressure tanks and in each independent pipe from the air supply to dry pipe systems.
   Gauges shall be graduated from zero to a pressure approximately double the normal working pressure of the system to which they are connected. Pressure gauges shall have a connection to the sprinkler system not less than one-quarter inch. Each gauge connection shall be equipped with a shutoff valve and provision for draining.
(Prior code §  91-34; Amend Coun. J. 10-30-96, p. 31216, § 1)