5804.2.3 Electrical equipment.
Electrical equipment within 3 feet (914 mm) in any direction of an outdoor flammable gas storage area shall comply with the Class I, Division 2 wiring requirements of the Electrical Code for hazardous locations, unless such electrical equipment is separated from such area by a wall or other solid partition having no openings.
5805.1 General.
Flammable gases in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(1) or 5003.1.1(3) shall be used in accordance with FC 5001, 5003 and 5005, and this chapter.
5806.1 Scope.
This section shall govern the storage, handling and use of flammable gas containing ethylene oxide used for sterilization purposes.
5806.2 General.
Flammable gases containing ethylene oxide used for sterilization purposes shall be stored, handled and used in compliance with the requirements of this chapter and FC Chapter 53. Ethylene oxide shall additionally be stored, handled and used in compliance with the requirements of NFPA 55.
5806.3 Design and installation requirements.
The design and installation of sterilization systems shall comply with the requirements of FC 5806.3.1 through 5806.3.7.