Loading...
5502.1 Definitions.
The following terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings set forth in FC 202.
CRYOGENIC CONTAINER.
CRYOGENIC FLUID.
FLAMMABLE CRYOGENIC FLUID.
LOW-PRESSURE CONTAINER.
MAXIMUM ALLOWABLE WORKING PRESSURE (MAWP).
5503.1 Cryogenic container.
Cryogenic containers shall comply with the requirements of FC 5503.1.1 through 5503.1.3.3 and FC Chapter 50.
5503.1.1 Cryogenic container standards.
Cryogenic containers shall be designed, constructed, operated and maintained in accordance with the ASME Boiler and Pressure Vessel Code or United States Department of Transportation regulations, or as otherwise approved.
5503.1.1.1 Pressure gauges.
Cryogenic containers shall be provided with pressure gauges. The maximum face reading for dial-type gauges shall not be less than 133 percent nor more than 250 percent of the MAWP of the cryogenic container.
5503.1.1.2 Liquid level-indicating devices.
Cryogenic containers shall be provided with a liquid level-indicating device. It shall be unlawful to use cryogenic containers with glass liquid level gauges in direct contact with the contents of such containers.
Loading...