Skip to code content (skip section selection)
Compare to:
Murrieta Overview
Murrieta, CA Municipal Code
Murrieta, California Municipal Code
Preface
Title 1 GENERAL PROVISIONS
Title 2 ADMINISTRATION AND PERSONNEL
Title 3 REVENUE AND FINANCE
Title 4 (RESERVED)
Title 5 BUSINESS LICENSES AND REGULATIONS
Title 6 ANIMALS
Title 7 (RESERVED)
Title 8 HEALTH AND SAFETY
Title 9 PUBLIC PEACE, MORALS AND WELFARE
Title 10 VEHICLES AND TRAFFIC
Title 11 (Reserved)
Title 12 STREETS, SIDEWALKS AND PUBLIC PLACES
Title 13 PUBLIC SERVICES
Title 14 (RESERVED)
Title 15 BUILDINGS AND CONSTRUCTION
Chapter 15.02 ADOPTION OF ADMINISTRATIVE PROVISIONS
Chapter 15.04 GENERAL*
Chapter 15.08 CALIFORNIA BUILDING STANDARDS CODES*
Chapter 15.12 UNIVERSAL DESIGN RESIDENTIAL DWELLINGS
Chapter 15.16 CALIFORNIA PLUMBING CODE*
Chapter 15.20 CALIFORNIA MECHANICAL CODE*
Chapter 15.24 CALIFORNIA FIRE CODE AND CALIFORNIA FIRE CODE STANDARDS
15.24.010 Adoption of the Fire Code.
15.24.020 Section 101.1 Amended - Title.
15.24.030 Section 102.13 Added - Repeal of conflicting ordinances, resolutions, or motions.
15.24.040 Section 103.1 Amended - Creation of an agency.
15.24.050 Section 107.2 Amended - Schedule of permit fees.
15.24.060 Section 107.4.1 Added - Fees for working or performing without necessary permits.
15.24.070 Section 107.7 Added - Cost recovery.
15.24.080 Section 107.8 Added - Reimbursement required.
15.24.090 Section 107.9 Added - Expense recovery.
15.24.100 Section 109.3.1 Added - Electronic recordkeeping.
15.24.110 Sections 111.1, 111.2, 111.3 & 111.4.
15.24.120 Section 112.4 Amended - Violation penalties.
15.24.130 Section 202 Added - General definitions.
15.24.140 Section 304.1.2 Amended - Vegetation.
15.24.150 Section 307.1.1 Amended - Prohibited open burning.
15.24.160 Section 307.6 Added - Outdoor fireplaces, fire pits, fire rings, or similar devices used at Group R occupancies.
15.24.170 Section 307.6.1 Added - Gas fueled devices.
15.24.180 Section 307.6.2 Added - Where prohibited.
15.24.190 Section 307.6.3 Added - Outdoor fireplaces utilizing wood or solid fuels.
15.24.200 Section 408 Added - Automated external defibrillators.
15.24.210 Section 501.1 Amended - Scope.
15.24.220 Section 503 Amended - Fire apparatus access roads.
15.24.230 Section 505.1 Amended - Address numbers.
15.24.240 Section 508 - Amended - Fire command center.
15.24.250 Section 510.1 Amended - Emergency responder communication coverage in new and existing buildings.
15.24.260 Section 901.6.3. Amended - Records.
15.24.270 Section 903.2 Amended - Where required.
15.24.280 Section 903.3.5.3 Amended - Hydraulically calculated systems.
15.24.290 Section 903.4 Amended - Sprinkler system supervision and alarms.
15.24.300 Section 907.1.6 Added - Fire alarm control panel (FACP).
15.24.310 Section 907.5.1 Amended - Occupant notification.
15.24.320 Section 914 Added - Mid-rise buildings.
15.24.330 Section 1205.2 Amended - Access and pathways.
15.24.340 Section 3313.1 Amended - When required.
15.24.350 Section 4911 Added - Fuel modification requirements for new construction.
15.24.360 Section 5001.5.2 Amended - Hazardous materials inventory statement (HMIS).
15.24.370 Section 5601.3.1 Amended - Prohibition.
15.24.380 Section 5601.3.2 Added - Seizure of fireworks.
15.24.390 Section 5608.2 Added - Firing.
15.24.400 Section 5614 Added - Explosives and blasting.
15.24.410 Section 5707.1 Added - General.
15.24.420 Chapter 80 Referenced Standards.
15.24.430 Amended - Table B105.1 (1).
15.24.440 Amended - Table B105.1(2).
Chapter 15.40 CALIFORNIA ELECTRICAL CODE*
Chapter 15.43 CALIFORNIA ENERGY CODE
Chapter 15.45 CALIFORNIA HISTORICAL BUILDING CODE
Chapter 15.46 CALIFORNIA EXISTING BUILDING CODE
Chapter 15.47 CALIFORNIA GREEN BUILDING STANDARDS CODE
Chapter 15.48 UNIFORM CODE FOR THE ABATEMENT OF DANGEROUS BUILDINGS
Chapter 15.50 SAFETY ASSESSMENT PLACARDS
Chapter 15.52 GRADING, EROSION AND SEDIMENT CONTROL
Chapter 15.54 ENCROACHMENT PERMITS GENERALLY
Chapter 15.56 FLOOD DAMAGE PREVENTION REGULATIONS
Chapter 15.60 CONVERSION OF EXISTING OVERHEAD LINES
Chapter 15.62 SMALL RESIDENTIAL ROOFTOP SOLAR ENERGY SYSTEM REVIEW AND PERMITTING PROCESS
Chapter 15.63 ELECTRIC VEHICLE CHARGING STATIONS
Title 16 DEVELOPMENT CODE
STATUTORY REFERENCES FOR CALIFORNIA CITIES
PRIOR CODE CROSS-REFERENCE TABLE
ORDINANCE LIST AND DISPOSITION TABLE
Loading...
15.24.250   Section 510.1 Amended - Emergency responder communication coverage in new and existing buildings.
   Requirements shall be provided in accordance with the ERCC guideline, provided by Murrieta Fire & Rescue and Murrieta Police Department.
(Ord. 584 § 1, 2022)
15.24.260   Section 901.6.3. Amended—Records.
   Records of all system inspections, tests, and maintenance required by referenced standards shall be submitted and maintained in the required format and electronically as required by the fire code official.
(Ord. 584 § 1, 2022)
15.24.270   Section 903.2 Amended—Where required.
   Approved automatic sprinkler systems, regardless of the occupancy classification, shall be provided throughout new buildings and structures which are 3,600 square feet or greater in size or more than two stories in height.
   Exception: Group R, occupancies shall comply with sections 903.2.8
   1.   Regardless of the occupancy classification. Where Sections 903.2.1 - 903.2.21 of the California Fire Code require more restrictive requirements than those listed below, the more restrictive requirement shall take precedence.
   2.   The elimination of sprinkler protection in the following areas is subject to approval by the Fire Code Official. Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries, and standby engines, provided those spaces or areas are equipped throughout with an automatic fire alarm system and are separated from the remainder of the building by fire barriers consisting of not less than 1-hour fire-resistance-rated walls and 2-hour fire-resistance-rated floor/ceiling assemblies.
   Unless required elsewhere in this code or the California Building Code, automatic fire sprinkler systems shall not be required for the following:
   1.   Detached Group U occupancies used for agricultural or livestock purposes, less than 5,500 square feet, and having setback distances of 50 feet or more from the property line and other buildings.
   2.   Detached non-combustible equestrian arena shade canopies that are open on all sides and used for riding only - no commercial, assembly or storage uses.
   3.   Detached fabric or non-combustible shade structures that are open on all sides and used to shade playground equipment, temporary storage of vehicles, and dining areas with no cooking.
   4.   Detached Group U occupancy greenhouses less than 5,500 square feet.
   5.   Where determined by the Fire Chief that no major life safety hazard exists, and the fuel load does not pose a significant threat to firefighter safety or to other structures or property, automatic fire sprinklers may be exempted.
   For development within the BP and Cl zoning districts or commercial or industrial buildings that are speculative in nature with no specific commodity or method of storage, the automatic fire protection system installed shall provide a minimum density coverage of 0.33/2,500 S.F. or as determined by the fire code official or their designee.
   Section 903.2.10 Amended - Group S-2 Parking Garages. An automatic sprinkler system shall be provided throughout buildings classified as parking garages.
   Section 903.2.10.1 Deleted - Commercial Parking Garages, is hereby deleted without replacement.
(Ord. 584 § 1, 2022)
15.24.280   Section 903.3.5.3 Amended— Hydraulically calculated systems.
   The design of hydraulically calculated fire sprinkler systems shall not exceed 90% of the water supply capacity.
(Ord. 584 § 1, 2022)
15.24.290   Section 903.4 Amended—Sprinkler system supervision and alarms.
   Section 903.4 Amended - Sprinkler System Supervision and Alarms is hereby amended by modifying items 1 and 2, deleting items 5 and 8, and renumbering the exceptions as follows:
   Exceptions:
      1.   Automatic sprinkler systems protecting one- and two-family dwellings.
      2.   Limited area systems serving fewer than 20 sprinklers.
      3.   Automatic sprinkler systems are installed in accordance with NFPA 13R where the common supply main is used to supply both the domestic and automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided.
      4.   Jockey pump control valves that are sealed or locked in the open position.
      5.   Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position.
      6.   Trim valves to pressure switches in dry, pre-action, and deluge sprinkler systems that are sealed or locked in the open position.
(Ord. 584 § 1, 2022)
15.24.300   Section 907.1.6 Added—Fire alarm control panel (FACP).
   The main fire alarm control panel shall be located in the same room as and share the same access as the fire sprinkler riser. The FACP shall have a minimum of 36 inches of face clearance and 6 inches of side clearance from any other wall or equipment.
(Ord. 584 § 1, 2022)
15.24.310   Section 907.5.1 Amended—Occupant notification.
   Required in multi-tenant buildings. In multi-tenant buildings, (including when a tenant improvement permit is required) where the automatic fire sprinkler bell cannot be heard within each of the tenant space(s), a single audio/visual device shall be installed in each suite, in a normally occupied location, and shall annunciate upon the activation of any fire protection system.
(Ord. 584 § 1, 2022)
15.24.320   Section 914 Added—Mid-rise buildings.
   Section 914.12 Added - General. A newly constructed mid-rise building shall comply with this section.
      Exceptions:
      1.   Buildings used exclusively as an open parking garage.
      2.   Buildings where all floors above the fourth-floor level are used exclusively as an open parking garage.
      3.   Buildings such as a power plant, lookout tower, steeple, grain house, and other similar structures with intermittent human occupancy.
   Section 914.12.1 Added - Automatic Fire Sprinkler Systems And Standpipes. Mid-rise buildings shall be protected throughout by an automatic fire sprinkler system designed and installed in conformance with the latest edition of NFPA 13 and in accordance with the following:
      1.   A shut-off valve and a water flow alarm shall be provided for each floor. Each shut-off valve and water flow alarm shall be electronically supervised.
      2.   Mid-rise buildings shall be provided with a Class I standpipe system that is interconnected with the automatic fire sprinkler system. The system shall consist of 2.5-inch hose valves located in each stair enclosure on every floor. Two hose outlets shall be located on the roof outside of each stair enclosure that penetrates the roof. The standpipe system shall be designed, installed, and tested in accordance with the latest edition of NFPA 14.
      3.   Fire department standpipe connections and valves serving each floor shall be located in the vestibule and located in a manner so as not to obstruct egress when hose lines are connected and charged.
   Section 914.12.2 Added - Smoke detection. Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system and shall be installed in accordance with the latest edition of NFPA 72. The actuation of any device required by this section shall operate the emergency voice alarm signal system and shall operate all equipment necessary to prevent the circulation of smoke through air returns and exhaust ductwork. Smoke detectors shall be located as follows:
      1.   In every mechanical equipment, electrical, transformer, telephone equipment, unmanned computer equipment, elevator machinery, or similar room and in all elevator lobbies. Elevator lobby detectors shall be connected to an alarm verification zone or be listed as a releasing device.
      2.   In the main return air and exhaust air plenum of each air conditioning system. The smoke detector shall be located in a serviceable area downstream of the last duct inlet.
      3.   At each connection to a vertical duct or riser serving no than 4 or more stories from a return air duct or plenum of an air conditioning system. In Group R,
         Division 1 and 2 occupancies, an approved smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cubic feet per minute and not serving more than 10 air inlet openings.
      4.   For Group R, Division 1 and 2 occupancies, in all corridors serving as a means of egress for an occupant load of 10 or more persons.
   Section 914.12.3 Added - Fire alarm system. An approved and listed, automatic and manual, fully addressable, and electronically supervised fire alarm system shall be provided in accordance with the provisions of this code and NFPA 72.
   Section 914.12.4 Added - Emergency voice alarm signaling system. The operation of any automatic fire detector or water flow device shall automatically sound an alert tone followed by a pre-recorded voice instruction giving appropriate information and direction on a general or selective basis to the following terminal areas:
      1.   Elevators
      2.   Elevator lobbies
      3.   Corridors
      4.   Exit stairways
      5.   Rooms and tenant spaces
      6.   Dwelling units
      7.   Hotel guest rooms
      8.   Areas designated as safe refuge within the building
   Section 914.12.5 Added - Fire Command Center. A fire command center for fire department operations shall be provided for mid-rise buildings, as defined in Section 202 of this ordinance, in accordance with Section 508.
   Section 914.12.6 Added - Elevators. Elevators and elevator lobbies shall comply with Chapter 30 of the California Building Code. At least one elevator cab shall be assigned for fire department use and shall serve all floors of the building. This cab shall be provided large enough to accommodate an ambulance-type stretcher in accordance with section 3002.4 of the California Building Code.
   Section 914.12.7 Added - Fire Department Communication System. An approved two-way fire department communication system designed and installed in accordance with the adopted edition of NFPA 72, shall be provided for fire department use per section 907.2.13.2.
   Section 914.12.8 Added - Means of egress. In addition to the requirements of Chapter 10, egress components of mid-rise buildings shall comply with sections 914.12.8.1 through 914.12.8.5.
   Section 914.12.8.1 Added - Extent of the enclosure. Stairway enclosures shall be continuous and shall fully enclose all portions of the stairway. Exit enclosures shall exit directly to the exterior of the building or include an exit passageway on the ground floor leading to the exterior of the building. Each exit enclosure shall extend completely through the roof and be provided with a door that leads onto the roof.
   Section 914.12.8.2 Added - Pressurized enclosures and stairways. All required stairways and enclosures in a mid-rise building shall be pressurized as specified in Section 909. Pressurized stairways shall be designed to exhaust smoke manually.
   Section 914.12.8.3 Added - Vestibules. Pressurized stairway enclosures serving a mid-rise building shall be provided with a pressurized entrance vestibule on each floor that complies with Section 909.
   Section 914.12.9.4 Added - Pressure differences. The minimum pressure difference between a vestibule and adjacent areas shall comply with Section 909.
   Section 914.12.8.5 Added -Locking of stairway doors. All stairway doors that are locked to prohibit access from the interior of the stairway shall have the capability of being unlocked simultaneously, without unlatching, upon a signal from the fire command center. Upon failure of normal electrical service or activation of any fire alarm, the locking mechanism shall automatically unlock.
(Ord. 584 § 1, 2022)
15.24.330   Section 1205.2 Amended—Access and pathways.
   Exception 3. Building-Integrated Photovoltaic (BIPV) systems where the BIPV systems are approved, integrated into the finished roof surface and are listed in accordance with a national test standard developed to address Section 690.12(B)(2) of the California Electrical Code. The removal or cutting away of portions of the BIPV system during firefighting operations shall not expose a firefighter to electrical shock hazards and smoke ventilation opportunity areas shall be identified.
(Ord. 584 § 1, 2022)
Loading...