15.24.430   Amended—Table B105.1 (1).
   TABLE B105.1(1)
   REQUIRED FIRE-FLOW FOR ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
 
CALCULATION AREA
(square feet)
AUTOMATIC SPRINKLER SYSTEM (Design Standard)
MINIMUM FIRE-FLOW
(gallons per minute)
FLOW DURATION (hours)
0-3,600
No automatic sprinkler system
1,500
2
3,601 and greater
No automatic sprinkler system
Value in Table B105.1(2)
Duration in Table B105.1(2) at the required fire-flow rate, but not less than 2 hours.
0-3,600
Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code
500
1/2
3,601 and greater
Section 903.3.1.3 of the California Fire Code or Section 313.3 of the California Residential Code
½ value in Table B105.1(2) but not less than 875
1
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m
 
(Ord. 584 § 1, 2022)