   TABLE B105.2
   REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES
 
AUTOMATIC SPRINKLER SYSTEM (Design Standard)
MINIMUM FIRE-FLOW (gallons per minute)
FLOW DURATION (hours)
No automatic sprinkler system
Value in Table B105.1(2)
Duration in Table B105.1(2)
Section 903.3.1.1 (NFPA 13) or Section 903.3.1.2 (NFPA13R) of the California Fire Code
50% of the value in Table B105.1(2) not less than 2,500 for multi-family, not less than 3,000 for commercial not less than 3,500 for industrial
Duration for multi-family, 2 hours
Duration for commercial, 3 hours Duration for industrial, 4 hours
For SI: 1 square foot = 0.0929 m2, 1 gallon per minute = 3.785 L/m *Or as otherwise required by the Fire Code official
 