(a) Doors shall be one and one-half hour Class B automatic closing except that when opening through a fire wall they shall provide fire resistance for such openings as required in Section 15-8-010 of this Code.
(b) Doors shall swing in the direction of the required exit travel.
(Prior code § 67-13.2)
(a) Bridges and balconies shall be constructed of noncombustible materials with solid floors. Railings shall comply with the requirements for railings of outside stairs.
(b) All exterior wall openings within a distance of 15 feet from balconies or bridges shall be protected by fire doors, fire windows or fire shutters as required in Section 15-8-070.
(Prior code § 67-13.3)
Escalators serving as a required means of exit shall comply with the requirements of Title 14C and with the requirements of Sections 13-160-530 to 13-160-570, inclusive.
(Prior code § 67-14; Amend Coun. J. 10-17-09, p. 72419, § 20; Amend Coun. J. 3-28-18, p. 74459, Art. II, § 18)
Escalators shall comply with all applicable requirements of interior stairways as provided in Section 13-160-290.
(Prior code § 67-14.1)