13-160-710  Directional signs – Where required.
   Exit, stairway, fire escape and directional signs shall be installed to mark all ways of egress in the following buildings or parts of buildings in the case of multiple occupancies:
   (a)   Multiple dwellings of the corridor type two stories or more in height;
   (b)   Institutional buildings two stories or more in height;
   (c)   Assembly units;
   (d)   Schools;
   (e)   Intermediate care facilities for the developmentally disabled – 15 or less;
   (f)   Business units, mercantile units, industrial units, storage units, and hazardous use units over two stories in height; business units, mercantile units, industrial units, storage units and hazardous use units two stories or less in height having a ground area of 10,000 square feet or more;
   (g)   Theatres;
   (h)   Churches;
   (i)   Open air assembly units with a capacity exceeding 250 persons where such unit is used at any time when natural light does not clearly indicate all means of egress.
(Prior code § 67-18.1; Amend Coun. J. 12-21-84, p. 12140)