13-160-400  Smokeproof towers – Opening protectives.
   (a)   The openings from the building to the vestibule or balcony and from the vestibule or balcony to the stair way enclosure shall be protected with self- closing Class B fire doors.
   (b)   All windows of the building or structure facing on a yard or court within 30 feet of the vestibule or balcony shall be protected with Class E fire doors, fire windows, fire shutters or other approved opening protectives complying with the requirements of Section 15-8-110.
(Prior code § 67-11.4)