Except as otherwise provided in Section 13-116-130, no building or structure of Type II or Type IV construction shall be erected within the fire limits, as defined in Section 13-116-010 nor shall wood or other combustible veneers be permitted on building or structures within such limits.
(Prior code § 50-2)
Buildings of Type IV-A and IV-B construction, when permitted, shall be located not less than six feet from interior lot lines and not less than 12 feet from any other building on the same lot with the following exceptions:
(a) A private garage may be located in accordance with Section 13-96-280.
(b) Any building except private detached garages, having exterior wall construction providing fire resistance of not less than one hour may be located not less than three feet from an interior lot line and not less than six feet from another building on the same lot.
(Prior code § 50-4; Amend Coun. J. 10-28-97, p. 54731)
Buildings of Type II construction, when permitted, shall be located not less than three feet from an interior lot line and not less than six feet from another building on the same lot unless the wall facing such lot line or adjoining building is constructed of materials providing fire resistance of not less than two hours and with all openings protected as required in Section 15-8-110.
(Prior code § 50-5)
Within the fire limits no building or structure shall be extended on any side by wood frame construction or unprotected noncombustible construction. When extensions are made to a building or structure of wood frame construction or unprotected noncombustible construction, the aggregate area of the building or structure including the extension shall not exceed the allowable area for wood frame construction in either Table 13-48-070 codified in Section 13-48-070 or Table 13-48-080 codified in Section 13-48-080.
(Prior code § 50-9)