Number of Stories Factor
2 1.00
3 0.90
4 0.85
5 0.80
6 0.75
7 0.70
8 or more 0.65
(See Table 13-48-080.)
(Prior code § 51-2.3)
Occupancy Classification | Construction Type | |||||||||
I-A | I-B | I-C | II | III-A | III-B | III-C | IV-A | IV-B |
Occupancy Classification | Construction Type | |||||||||
I-A | I-B | I-C | II | III-A | III-B | III-C | IV-A | IV-B | ||
A. | Residential | NL | NL | 20,000 | NP | 8,000 | 8,000 | 6,000 | 4,000 | 2,000 |
B. | Institutional | 30,000 | 16,000 | 12,000 | NP | NP | NP | NP | NP | NP |
C-1. | Assembly | NL | NL | 16,000 | NP | 6,000 | 6,000 | NP | NP | NP |
C-2. | Small Assembly | NL | NL | 16,000 | NP | 6,000 | 6,000 | NP | NP | NP |
C-3. | Schools | NL | NL | 16,000 | NP | 6,000 | 6,000 | NP | NP | NP |
D. | Open Air Assembly | Maximum areas established in Chapter 55 | ||||||||
E. | Business | NL | NL | 20,000 | NP | 10,000 | 10,000 | 8,000 | NP | NP |
F. | Mercantile | 30,000 | 20,000 | 16,000 | NP | 8,000 | 8,000 | 6,000 | NP | NP |
G-1. | Industrial Low-Hazard | NL | 30,000 | 20,000 | 10,000 | 10,000 | 10,000 | 8,000 | NP | NP |
G-2. | Industrial Moderate- Hazard | 30,000 | 20,000 | 16,000 | NP | 8,000 | 8,000 | 6,000 | NP | NP |
H-1. | Storage Low-Hazard | NL | 30,000 | 20,000 | 10,000 | 10,000 | 10,000 | 8,000 | NP | NP |
H-2. | Storage Moderate- Hazard | 30,000 | 20,000 | 16,000 | NP | 8,000 | 8,000 | 6,000 | NP | NP |
H-3. | Garages | 25,000 | 15,000 | 10,000 | NP | 6,000 | 6,000 | NP | NP | NP |
I. | Hazardous-Use | Maximum areas established in Chapter 60 | ||||||||
J. | Miscellaneous Buildings & Structures | Maximum areas established in Chapter 61 | ||||||||
NOTES: | ||||||||||
NL – Not Limited. In buildings of unlimited area, no portion of such buildings shall be more than 300 feet from an exterior wall facing an open, accessible space not less than 30 feet wide consisting of a public way, railroad right-of-way, waterway, park or a court, accessible from a public way; except that such maximum distance from an exterior wall may not be more than 500 feet in buildings of low hazard industrial or low hazard storage units. | ||||||||||
NP – Not Permitted. | ||||||||||
See Section 13-48-090 for allowable increase in areas for frontage and automatic sprinkler equipment. | ||||||||||