9-1B-48: IRC ONE-AND-TWO-FAMILY DWELLING BUILDING CODE AMENDMENT, TABLE R403.1(1) MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS FOR LIGHT-FRAME CONSTRUCTION, TABLE R403.1(2) MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS FOR LIGHT-FRAME CONSTRUCTION WITH BRICK VENEER, TABLE R403.1(3) MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS WITH CAST-IN-PLACE OR FULLY GROUTED MASONRY WALL CONSTRUCTION, AND TABLE R403.4 MINIMUM DEPTH (D) AND WIDTH (W) OF CRUSHED STONE FOOTINGS, ARE DELETED:
Table R403.1(1) Minimum Width And Thickness For Concrete Footings For Light-Frame Construction, Table R403.1(2) Minimum Width And Thickness For Concrete Footings For Light-Frame Construction With Brick Veneer, Table R403.1(3) Minimum Width And Thickness For Concrete Footings With Cast-In-Place Or Fully Grouted Masonry Wall Construction, and Table R403 Minimum Depth (D) and Width (W) Of Crushed Stone Footings, are hereby deleted.
(Ord. 40-20, 12-1-2020, eff. 1-1-2021)
Add Table R403.1, Minimum Width Of Concrete, Precast, Or Masonry Footings as follows:
TABLE R403.1
MINIMUM WIDTH OF CONCRETE, PRECAST, OR MASONRY FOOTINGS (inches)a
LOAD-BEARING VALUE OF SOIL (psf) | ||||
1,500 | 2,000 | 3,000 | 4,000 |
LOAD-BEARING VALUE OF SOIL (psf) | ||||
1,500 | 2,000 | 3,000 | 4,000 | |
Conventional light-frame construction | ||||
1-Story | 12 | 12 | 12 | 12 |
2-Story | 15 | 12 | 12 | 12 |
3-Story | 23 | 17 | 12 | 12 |
4-inch brick veneer over light-frame or 8-inch hollow concrete masonry | ||||
1-Story | 12 | 12 | 12 | 12 |
2-Story | 21 | 16 | 12 | 12 |
3-Story | 32 | 24 | 16 | 12 |
8-inch solid or fully grouted masonry | ||||
1-Story | 16 | 12 | 12 | 12 |
2-Story | 29 | 21 | 14 | 12 |
3-Story | 42 | 32 | 21 | 16 |
For SI: 1 inch = 25.4mm, 1 pound per square foot = 0.0479 kPa.
a. Where minimum footing width is twelve (12) inches, use of a single wythe of solid or fully grouted twelve (12) inch nominal concrete masonry units is permitted.
(Ord. 40-20, 12-1-2020, eff. 1-1-2021)
Repeal Section R403.1.1, Minimum size, and replace as follows:
R403.1.1 Minimum size. Minimum sizes for concrete and masonry footings shall be as set forth in Table R403.1 and Figure R403.1(1). The footing width (W) shall be based on the load bearing value of the soil in accordance with Table R401.4.1. Spread footings shall be at least six (6) inches in thickness (T). Footing projections (P) shall be at least two (2) inches and shall not exceed the thickness of the footing. The size of
footings supporting piers and columns shall be based on the tributary load and allowable soil pressure in accordance with Table R401.4.1. Footings for wood foundations shall be in accordance with the details set forth in Section R403.2 and Figures R403.1(2) and R403.1(3).
(Ord. 40-20, 12-1-2020, eff. 1-1-2021)
R602.10 Wall bracing. Buildings shall be braced in accordance with this section or, when applicable, section R602.12 or the most current version of APA System Report SR-102 at the time of application for a permit as an alternate method. Where a building, or portion thereof, does not comply with one or more of the bracing requirements in this section, those portions shall be designed and constructed in accordance with section R301.1.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 40-20, 12-1-2020, eff. 1-1-2021)
R903.1 General. Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof coverings shall be designed, installed, and maintained in accordance with this code and the approved manufacturer's installation instructions such that the roof covering shall serve to protect the building or structure. Roof covering requirements for hillside and Wildland Urban Interface areas are to be as regulated by the Fire Prevention Code, of Boise City Code.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 40-20, 12-1-2020, eff. 1-1-2021)