9-1B-35: IRC ONE-AND-TWO-FAMILY DWELLING BUILDING CODE AMENDMENT, TABLE R302.1(1), EXTERIOR WALLS:
Table R302.1(1) shall be amended as follows:
   TABLE R302.1(1)
   EXTERIOR WALLS
Exterior Wall Element
Minimum Fire- Resistance Rating
Minimum Fire Separation Distance
Exterior Wall Element
Minimum Fire- Resistance Rating
Minimum Fire Separation Distance
Walls
Fire- resistance rated
1 hour-tested in accordance with ASTM E119, UL 263, or Section 703.3 of the International Building Code with exposure from both sides
<3 feet
Not fire- resistance rated
0 hours
3 feet
Projections
Fire- resistance rated
1 hour on the underside, or heavy timber, or fire retardant-treated wooda,b
2 feet to <3 feet
Not fire- resistance rated
0 hours
3 feet
Openings in walls
Not allowed
N/A
<3 feet
25% maximum of wall area
0 hours
3 feet to <5 feet
Unlimited
0 hours
5 feet
Penetrations
All
Comply with Section R302.4
<3 feet
None required
3 feet
 
   For SI: 1 foot = 304.8 mm.
   N/A = Not Applicable.
   a.   The fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the eave overhang if fireblocking is provided from the wall top plate to the underside of the roof sheathing.
   b.   The fire-resistance rating shall be permitted to be reduced to zero (0) hours on the underside of the rake overhang where gable vent openings are not installed.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 40-20, 12-1-2020, eff. 1-1-2021)