R109.1.3 Floodplain Inspections. For construction in flood hazard areas as established by Table R301.2(1), in addition to the initial elevation certificate required at time of permit application, upon placement of the lowest floor, including basement, the building official or designee shall require submission of documentation, prepared by persons as specified in the Flood Hazard regulations of the Boise Development Code, of the elevation of the lowest floor, including basement, required in Section R322 prior to the request for a framing inspection.
(Ord. 44-17, 12-19-2017, eff. 1-1-2018; amd. Ord. 40-20, 12-1-2020, eff. 1-1-2021)