Table R301.2(1) is revised to include the climatic and geographic design criteria for Philadelphia as follows:
GROUND SNOW LOAD | WIND SPEED d (mph) | SEISMIC DESIGN CATEGORY f |
SUBJECT TO DAMAGE FROM | WINTER DESIGN TEMP e |
ICE BARRIER UNDER- LAYMENT REQUIRED
h | FLOOD HAZARDS g |
AIR FREEZING INDEX
i |
MEAN ANNUAL TEMP j | ||
Weathering
a |
Frost line depth
b |
Termite
c | ||||||||
25 psf | 115 | B | Severe | 30 in. | Moderate to heavy | 14° F | YES | 500 | 55.9° F |
Insert Table R-R301.2(1a) as follows
PANEL NUMBER
|
EFFECTIVE
|
PANEL NUMBER
|
EFFECTIVE
|
420757IND0B | 11/18/2015 |
4207570019G | 01/17/2007 |
4207570038G | 01/17/2007 |
4207570067G | 01/17/2007 |
4207570078G | 01/17/2007 |
4207570086G | 01/17/2007 |
4207570087G | 01/17/2007 |
4207570088G | 01/17/2007 |
4207570089G | 01/17/2007 |
4207570104G | 01/17/2007 |
4207570107G | 01/17/2007 |
4207570108G | 01/17/2007 |
4207570109G | 01/17/2007 |
4207570111G | 01/17/2007 |
4207570113G | 01/17/2007 |
4207570114H | 11/18/2015 |
4207570116G | 01/17/2007 |
4207570117H | 11/18/2015 |
4207570118H | 11/18/2015 |
4207570119H | 11/18/2015 |
4207570126G | 01/17/2007 |
4207570127G | 01/17/2007 |
4207570128G | 01/17/2007 |
4207570129G | 01/17/2007 |
4207570136H | 11/18/2015 |
4207570157G | 01/17/2007 |
4207570159G | 01/17/2007 |
4207570167G | 01/17/2007 |
4207570169H | 11/18/2015 |
4207570177G | 01/17/2007 |
4207570178G | 01/17/2007 |
4207570179G | 01/17/2007 |
4207570181G | 01/17/2007 |
4207570182H | 11/18/2015 |
4207570183G | 01/17/2007 |
4207570184H | 11/18/2015 |
4207570186H | 11/18/2015 |
4207570187H | 11/18/2015 |
4207570188H | 11/18/2015 |
4207570189H | 11/18/2015 |
4207570191H | 11/18/2015 |
4207570192H | 11/18/2015 |
4207570193H | 11/18/2015 |
4207570194H | 11/18/2015 |
4207570201H | 11/18/2015 |
4207570202H | 11/18/2015 |
4207570203H | 11/18/2015 |
4207570206H | 11/18/2015 |
4207570230H | 11/18/2015 |
Pursuant to the UCC, delete Section R302.5.1 and replace as follows:
R-R302.5.1 Opening protection. Openings from a private garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with solid wood doors not less than 1-3/8 inches (35 mm) in thickness, solid or honeycomb core steel doors not less than 1-3/8 inches (35 mm) thick, or 20-minute fire-rated doors.
Delete Section R310.6 and replace as follows:
Exception: New sleeping rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section R310.1.
Pursuant to the UCC, delete Section R311.7.4 and replace as follows:
R-R311.7.4 Walkline. The walkline across winder treads and landings shall be concentric to the turn and parallel to the direction of travel entering and exiting the turn. The walkline shall be located 12 inches (305 mm) from the inside of the turn. The 12-inch (305 mm) dimension shall be measured from the widest point of the clear stair width at the walking surface. Where winders are adjacent within a flight, the point of the widest clear stair width of the adjacent winders shall be used.

Pursuant to the UCC, delete Section R311.7.5 and replace as follows:
R-R311.7.5.1 Risers. The riser height shall be not more than 8-1/4 inches (210 mm). The riser shall be measured vertically between leading edges of the adjacent treads. The greatest riser height within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Risers shall be vertical or sloped from the underside of the nosing of the tread above at an angle not more than 30 degrees (0.51 rad) from the vertical. Open risers are permitted provided that the openings located more than 30 inches (762 mm), as measured vertically, to the floor or grade below do not permit the passage of a 4-inch diameter (102 mm) sphere.
Exceptions:
1. The opening between adjacent treads is not limited on spiral stairways.
2. The riser height of spiral stairways shall be in accordance with Section R311.7.10.1.
R-R311.7.5.2 Treads. The tread depth shall be not less than 9 inches (229 mm). The tread depth shall be measured from tread nosing to tread nosing. The greatest tread depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Treads may have a uniform projection of not more than 1-1/2 inches (38 mm) when solid risers are used.
R-R311.7.5.2.1 Winder Treads. Winder treads shall have a tread depth of not less than 10 inches (254 mm) measured between the vertical planes of the foremost projection of adjacent treads at the intersections with the walkline. Winder treads shall have a tread depth of not less than 6 inches (152 mm) at any point within the clear width of the stair. Within any flight of stairs, the largest winder tread depth at the walkline shall not exceed the smallest winder tread by more than 3/8 inch (9.5 mm). Consistently shaped winders at the walkline shall be allowed within the same flight of stairs as rectangular treads and shall not be required to be within 3/8 inch (9.5 mm) of the rectangular tread depth.
Exception: The tread depth at spiral stairways shall be in accordance with Section R311.7.10.1.
Loading...