803.10 Installation.
Connectors shall be installed in accordance with Sections 803.10.1 through 803.10.6.
803.10.1 Supports and joints.
Connectors shall be supported in an approved manner, and overlapping joints shall be tight-fitting and fastened with sheet metal screws, rivets, welds or other approved means.
803.10.2 Length.
The maximum horizontal length of a single- wall connector shall not affect the capability of the system to produce adequate draft.
803.10.3 Connection.
The connector shall extend to the inner face of the chimney or vent liner, but not beyond. A connector entering a masonry chimney shall be cemented to masonry in an approved manner. Where thimbles are installed to facilitate removal of the connector from the masonry chimney, the thimble shall be permanently cemented in place with high-temperature cement.