15-24-790 Fire-extinguishing equipment.
   Fire extinguishing equipment shall be provided as follows:
   (a)   Standard fire extinguishers shall be required.
   (b)   Dip tanks having less than 150 gallons capacity or less than ten square feet liquid surface area shall be fitted with a cover complying with the provisions of Section 15-24-800 or with one of the automatic extinguishing facilities specified below.
   (c)   Dip tanks of over 150 gallons capacity or having a liquid surface area in excess of ten square feet shall be protected with at least one of the following automatic extinguishing facilities:
      1.   An approved automatic water spray extinguishing system;
      2.   An approved automatic foam extinguishing system;
      3.   An approved automatic carbon dioxide extinguishing system;
      4.   An approved automatic dry chemical extinguishing system.
(Prior code §  129.1-70)