Aggregate Capacity of Cylinder Groups |
Groups of Cylinders and Buildings on the Same Property | Between Cylinder Storage Groups | Between Groups of Cylinders and Adjoining Property | Groups of Cylinders and Buildings Occupied as Institutional, Assembly or Open Air Assembly |
2,500 lbs. or less | None See Note 1 and 2 | 10 | 10 | 100 |
2,501 to 6,000 lbs. | 25 | 25 | 25 | 250 |
6,001 to 10,000 lbs. | 50 | 50 | 50 | 250 |
Over 10,000 lbs. | 75 | 75 | 75 | 250 |
Note 1. Storage must be ten feet away from door opening.
Note 2. The discharge from safety relief devices shall be located not less than three feet horizontally away from any building opening which is below the level of such discharge.