15-26-550  Repair and renovation use – Restrictions.
   Containers of liquefied petroleum gas may be used in multiple-dwelling units, business units and mercantile units in connection with repair and renovation operations only under the following conditions:
   1.   The maximum water capacity of individual containers shall be 50 pounds (20 pounds of liquefied petroleum gas);
   2.   The number of liquefied petroleum gas containers shall not exceed the number of workmen assigned to using the liquefied petroleum gas;
   3.   Containers of greater than two and one-half pounds water capacity shall not be left unattended in such buildings.
(Coun. J. 12-9-92, p. 25465; Amend Coun. J. 2-7-96, p. 15616)