13-64-141  Smoke detection system in lieu of smoke alarms.
   Smoke detectors listed in accordance with UL 268-09 and provided as part of the building fire alarm system shall be an acceptable alternative to single- and multiple-station smoke alarms and shall comply with the following:
   (1)   The fire alarm system shall comply with all applicable requirements in Chapter 15-16.
   (2)   Activation of a smoke detector in a dwelling unit or sleeping area other than a dwelling unit shall initiate alarm notification in the dwelling unit or sleeping area.
   (3)   Activation of a smoke detector in a dwelling unit or sleeping area other than a dwelling unit shall not activate alarm notification appliances outside of the dwelling unit or sleeping area, provided that a supervisory signal is generated and monitored in accordance with Chapter 15-16.
(Added Coun. J. 9-6-17, p. 55278, Art. VI, § 11)