Every hazardous use unit shall be separated from every other hazardous use unit and from every other occupancy in the same building by construction of the character as required by Chapters 15-24, 15-26 and 15-28 and Sections 13-56-280 and 13-112-010 of this Code.
(Prior code § 60-9; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 11-9-16, p. 36266, § 24)
There shall be no opening between a hazardous use unit and any adjoining or adjacent building except in the ground story or first story; provided, however, that adjoining and adjacent hazardous use units of the same class of occupancy which are used by the same person may have communication on any floor, subject to the applicable provisions of Section 13-56-280 of this Code.
(Prior code § 60-10)
Every court used in part for the purposes of a hazardous use unit and in part for any other purpose shall meet the most restrictive requirements in the building provisions of this Code for a court for any of the purposes for which the building is designed, erected, altered or used.
(Prior code § 60-11)
ARTICLE III. ROOMS AND FLOOR AREAS (13-112-120 et seq.)
The requirements of this Code relating to size and location of rooms in an industrial or storage unit, shall apply to a hazardous use unit in accordance with the provisions of Section 13-112-110 except as otherwise provided by Chapters 15-24, 15-26 and 15-28 of this Code.
(Prior code § 60-12; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 11-9-16, p. 36266, § 24)
None of the following herein described hazardous use units:
Asphalt, tar, pitch, resin or paraffin heating room;
Corrosive liquid storage room;
Dip tanks having a capacity or liquid surface area in excess of the following:
Capacity | Liquid Surface Area | |
Class I | 10 gallons | 4 square feet |
Class II | 60 gallons | 10 square feet |
Class III | 125 gallons | 15 square feet |
Drying room for any article or material which will give off explosive or flammable vapors during the drying process;
Flammable liquids storage (except as provided in Section 15-24-270 of this Code);
Fume or flammable compressed gas;
Grinding or dust producing;
Hazardous chemical;
Highly flammable material storage;
Highly toxic materials;
Japanning or enameling;
Nitrocellulose products;
Paint spraying or mixing except for water base paint;
Picker or shredder;
Standard fireproof vault;
Sulphur storage;
shall be located in any story below grade in any building hereafter designed, erected, altered or converted for any purpose; provided, however, that one or more rooms built for no purpose other than that of the operation of water purification plants or a refrigerating unit may be located in any basement of any building.
(Prior code § 60-14)