All lighting attached to fuel canopies within Zone C shall meet the following additional requirements:
(a) The maintained illuminance levels shall not exceed 120 percent of IES- recommended practice for low ambient light zones; and
(b) Luminaires for new and rebuilt canopies are to be recessed or semi-recessed into the canopy and possess a flat lens that resides at ≤ 2.5 inches below the canopy ceiling. Replacement luminaires for existing canopies may be surface mounted as long as there is a flat lens and it resides higher than the bottom edge of the perimeter canopy structure. Neither external nor internal lighting of the perimeter structure is allowed unless it exists at the time this updated ordinance was adopted, and then still needs to be brought into compliance within 10 years from the date of adoption of this ordinance.
(Added by Ord. No. 10691 (N.S.), effective 12-18-20)