Skip to code content (skip section selection)
Compare to:
New York City Overview
The New York City Charter
The New York City Administrative Code
The Rules of the City of New York
THE RULES OF THE CITY OF NEW YORK
Title 1: Department of Buildings
Title 2: Board of Standards and Appeals
Title 3: Fire Department
Chapter 1: Administration
Chapter 2: Definitions
Chapter 3: General Precautions Against Fire
Chapter 4: Emergency Planning and Preparedness
Chapter 5: Fire Operations Features
Chapter 6: Building Services and Systems
Chapter 7: Fire-Resistant Rated Construction
Chapter 8: Interior Furnishings, Decorations and Scenery
Chapter 9: Fire Protection Systems
Chapter 10: Means of Egress
Chapter 11: Reserved
Chapter 12: Reserved
Chapter 13: Reserved
Chapter 14: Reserved
Chapter 15: Reserved
Chapter 16: Reserved
Chapter 17: Reserved
Chapter 18: Reserved
Chapter 19: Reserved
Chapter 20: Aviation Facilities and Operations
Chapter 21: Dry Cleaning
Chapter 22: Combustible Dust-Producing Operations
Chapter 23: Motor Fuel Dispensing Facilities and Repair Garages
Chapter 24: Flammable Finishes
Chapter 25: Fruit and Crop Ripening
Chapter 26: Fumigation and Insecticidal Fogging
Chapter 27: Semiconductor Fabrication Facilities
Chapter 28: Lumbar Yards and Wood Waste Materials
Chapter 29: Manufacture of Organic Coatings
Chapter 30: Industrial Furnaces
Chapter 31: Tents and Other Membrane Structures
Chapter 32: High-Piled Combustible Storage
Chapter 33: Fire Safety During Construction, Alteration, and Demolition
Chapter 34: Tire Rebuilding and Tire Storage
Chapter 35: Welding and Other Hot Work
Chapter 36: Marinas
Chapter 37: Combustible Fibers
Chapter 38: Reserved
Chapter 39: Reserved
Chapter 40: Distilleries
Chapter 41: Reserved
Chapter 42: Reserved
Chapter 43: Reserved
Chapter 44: Reserved
Chapter 45: Reserved
Chapter 46: Reserved
Chapter 47: Reserved
Chapter 48: Reserved
Chapter 49: Reserved
Chapter 50: Hazardous Materials - General Provisions
Chapter 51: Aerosols
Chapter 52: Reserved
Chapter 53: Compressed Gases
Chapter 54: Corrosive Materials
Chapter 55: Cryogenic Fluids
Chapter 56: Explosives, Fireworks and Special Effects
Chapter 57: Flammable and Combustible Liquids
Chapter 58: Flammable Gases
Chapter 59: Flammable Solids
Chapter 60: Highly Toxic and Toxic Materials
Chapter 61: Liquefied Petroleum Gases
Chapter 62: Organic Peroxides
Chapter 63: Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids
Chapter 64: Pyrophoric Materials
Chapter 65: Pyroxylin Plastics
Chapter 66: Unstable (Reactive) Materials
Chapter 67: Water-Reactive Solids and Liquids
Chapter 68: Reserved
Chapter 69: Reserved
Chapter 70: Reserved
Chapter 71: Reserved
Chapter 72: Reserved
Chapter 73: Reserved
Chapter 74: Reserved
Chapter 75: Reserved
Chapter 76: Reserved
Chapter 77: Reserved
Chapter 78: Reserved
Chapter 79: Reserved
Chapter 80: Referenced Standards
Chapter 81: Fees
Chapter 82: Referenced Standard Modifications
Chapter 83: Pre-Existing Facilities
Chapter 84: Miscellaneous
Title 6: Department of Consumer and Worker Protection
Title 9: Procurement Policy Board Rules
Title 12: Franchise and Concession Review Committee
Title 15: Department of Environmental Protection
Title 16: Department of Sanitation
Title 17: Business Integrity Commission
Title 19: Department of Finance
Title 20: Tax Appeals Tribunal
Title 21: Tax Commission
Title 22: Banking Commission
Title 24: Department of Health and Mental Hygiene
Title 25: Department of Mental Health and Retardation [Repealed]
Title 28: Housing Preservation and Development
Title 29: Loft Board
Title 30: Rent Guidelines Board
Title 31: Mayor's Office of Homelessness and Single Room Occupancy
Title 34: Department of Transportation
Title 35: Taxi and Limousine Commission
Title 38: Police Department
Title 38-A: Civilian Complaint Review Board
Title 39: Department of Correction
Title 40: Board of Correction
Title 41: Department of Juvenile Justice
Title 42: Department of Probation
Title 43: Mayor
Title 44: Comptroller
Title 45: Borough Presidents
Title 46: Law Department
Title 47: Commission on Human Rights
Title 48: Office of Administrative Trials and Hearings (OATH)
Title 49: Department of Records and Information Services
Title 50: Community Assistance Unit
Title 51: City Clerk
Title 52: Campaign Finance Board*
Title 53: Conflicts of Interest Board
Title 55: Department of Citywide Administrative Services
Title 56: Department of Parks and Recreation
Title 57: Art Commission
Title 58: Department of Cultural Affairs
Title 60: Civil Service Commission
Title 61: Office of Collective Bargaining
Title 62: City Planning
Title 63: Landmarks Preservation Commission
Title 66: Department of Small Business Services
Title 67: Department of Information Technology and Telecommunications
Title 68: Human Resources Administration
Title 69: Department of Aging
Title 70: In Rem Foreclosure Release Board
Title 71: Voter Assistance Commission
Title 72: Office of Emergency Management
Title 73: Civic Engagement Commission
Title 74: Community Hiring
Chapter 9: Fire Protection Systems
§ 901-01 Central Station Monitoring of Fire Alarm Systems.
   (a)   Scope. This section sets forth standards, requirements and procedures for:
      (1)   the monitoring and related maintenance of all fire alarm systems that are installed in premises located in New York City and that transmit an alarm signal to a central station that monitors such systems for the purpose of re-transmitting or otherwise reporting fire alarms to the Department; and
      (2)   the operation of the central stations that monitor and maintain fire alarm systems.
   (b)   Definitions. The following terms shall, for purposes of this section and used elsewhere in the rules, have the meanings shown herein:
      Alarm service. The service provided by a central station company commencing upon the transmission from the protected premises of an alarm signal, a supervisory signal, or a trouble signal.
      Approved central station company. A central station company that has been issued a valid certificate of operation.
      Central station company. A person or entity engaged in the operation of a central station.
      Central station signaling system. A system comprised of the protective signaling system at the protected premises, the central station physical plant, the exterior communications channels, and satellite stations, if any.
      Designated representative. A person or entity designated by the subscriber who shall be responsible for receiving notifications from the central station company concerning the status of the protective signaling system at the protected premises and who is authorized to take action with respect to such system.
      Mandatory system. A protective signaling system whose installation at a protected premises is required by law.
      Proprietary central station. A central station operated by or on behalf of the owner of the protected premises monitored by the central station, that monitors protected premises other than the premises in which the central station is located. For purposes of this section and 3 RCNY § 8104-01, unless otherwise specifically provided, reference to "central station company" shall be deemed to include proprietary central stations.
      Protective signaling system. A system or device installed at a protected premises and designed to transmit an alarm signal, a supervisory signal or a trouble signal.
      Runner service. The dispatching to the protected premises of individuals designated by a central station company, other than the required number of operators on duty to monitor signals, to silence, reset and otherwise restore the protected signaling system to normal service. Such runners may be employees of the central station company, another approved central station company, or a service retained by the central station company, provided that the individuals are trained in and knowledgeable of the protective signaling systems for which they are providing runner service.
      Subscriber. An owner of a protected premises, or an owner of a fire alarm system installed on such a premises, who has arranged for a central station company to monitor the fire alarm system on the protected premises for the purpose of reporting fire alarms to the Department.
      Terminal. A number assigned by the Department which indicates a specific location and/or type of alarm signal at a protected premises.
      Transmitter. A component of a protective signaling system that provides the link between a fire alarm system and the transmission channels.
      Voluntary system. A protective signaling system whose installation at a protected premises is not required by law.
   (c)   Prohibited Fire Alarm System Monitoring. It shall be unlawful for:
      (1)   Any person or entity, pursuant to FC 901.6.3.5, to operate a central station company or central station that monitors fire alarm systems in protected premises without having first obtained a certificate of operation pursuant to 3 RCNY § 115-01. A central station company shall obtain a certificate of operation prior to operating any central station or transmitting any alarms to the Department received from a protected premises.
      (2)   Any owner of a protected premises, or other person or entity to contract for, arrange, or otherwise cause or allow, a central station company to receive or retransmit alarm signals from a protected premises, unless such central station company possesses a valid certificate of operation. This provision shall apply whether the protective signaling system installed at a protected premises is a mandatory or voluntary system.
   (d)   General Provisions.
      (1)   Applicable provisions of law. All central stations and proprietary central stations shall be designed, installed, operated and maintained in compliance with the requirements of FC Chapter 9, this section and NFPA 72. The relationship between the provisions of the Fire Code, this section and such referenced standard shall be as set forth in FC 102.6.2.
      (2)   Compliance with Building Code and Electrical Code. All central stations and proprietary central stations shall be designed, installed, operated and maintained in compliance with the requirements of the Building Code and the Electrical Code.
   (e)   Central Stations. Central stations shall comply with the following design and installation requirements.
      (1)   Security. The central station operating room shall be locked at all times and access restricted to authorized persons only.
      (2)   Emergency power. Emergency power shall be provided for the exclusive use of the operating room and other areas vital to the continuous operation of the central station and its provision of fire alarm monitoring services. The emergency power supply shall function automatically upon failure of the normal power supply system. Emergency power systems shall be maintained in accordance with FC 604.
      (3)   Listed equipment. The central station shall be equipped with devices, equipment and systems capable of automatically receiving and recording signals, as required by NFPA 72. Such devices, equipment and systems shall be listed by Factory Mutual, Underwriters Laboratories or other approved nationally recognized testing laboratory.
      (4)   Circuit adjusting equipment. Circuit adjusting instruments or equipment for emergency operations may be automatically initiated or manually operated upon receipt of a trouble signal.
      (5)   Retransmission of alarm signals. The retransmission of an alarm signal received at the Department shall be effected as follows:
         (A)   by the use of two (2) telephone lines provided with suitable voice transmitting, receiving and automatic recording equipment, provided that these lines shall not be used for any purpose except communication between the Department and the central station and shall have terminal equipment located at the central station and the Department and shall be provided with twenty-four hour standby power; or
         (B)   any other means of retransmission deemed by the Commissioner to effect a retransmission at a level of reliability that equals or exceeds that under 3 RCNY § 901-01(e)(5)(A).
      (6)   Alternative voice communication capabilities. The company shall maintain at each central station at least one cellular telephone available for communication with the Department and the protected premises in the event that telephone circuitry is inoperable.
      (7)   The central station company shall bear all costs associated with the retransmission of fire alarm signals to the Department, including any costs incurred by the Department.
   (f)   Central Station Operations.
      (1)   General responsibilities. A central station company shall be accountable to its subscriber to provide all of the requirements of this section, and shall set forth such obligation in its contract with the subscriber. In all cases where an approved central station company has subcontracted with another entity to provide services, the central station company shall be responsible for ensuring that the services provided by the subcontractor comply with this section and with all other applicable laws, rules, regulations and reference standards. A central station company may not subcontract signal monitoring or retransmission services or maintenance to a separate entity unless said separate entity is itself an approved central station company.
      (2)   Maintenance of central stations and transmitters.
         (A)   A central station company shall be responsible for the maintenance of its central stations and the transmitters at protected premises within New York City monitored by such central stations. A central station company shall have available at all times designated individuals trained and knowledgeable in the maintenance and repair of central station devices, equipment and systems, including transmitters, so as to prevent or minimize any disruptions in fire alarm system monitoring. Such individuals shall be employees of the central station company (other than the required number of operators on duty to monitor signals); another approved central station company; or of the holder of a fire alarm installer license issued by the New York Secretary of State pursuant to Article 6-D of the New York State General Business Law or a master electrician licensed by the Department of Buildings and registered with the New York Secretary of State in accordance with such Article 6-D, who has been retained to provide such service. In the event of a malfunction, repairs shall be immediately undertaken so as to restore proper operation and system monitoring as soon as possible.
         (B)   A central station company shall ensure that a complete and satisfactory test of all transmitters is conducted at each protected premises in compliance with the requirements of NFPA 72.
         (C)   A central station company shall test all paths of communication for the central station signaling system that are not supervised at least once every twelve hours. A record of such tests shall be maintained in the central station log.
      (3)   Monitoring of fire alarm systems.
         (A)   A central station company shall have sufficient personnel on duty at all times to ensure immediate attention to all signals received. This shall include a minimum of two (2) operators at each central station, each of whom shall possess a certificate of fitness to operate central station equipment. A trainee functioning as an operator must work under the direct supervision and in the presence of an operator holding a certificate of fitness and may not be counted as one of the two (2) operators holding certificates of fitness as required by this section.
         (B)   Central station operators shall monitor and process all fire alarm signals before any other signals, regardless of the order in which they are received.
         (C)   Alarm signals shall be re-transmitted to the Department immediately upon receipt of the full signal at the central station. A full signal is deemed to be received at the time it is capable of being decoded.
         (D)   Alarm signals transmitted to the Department shall indicate the type of alarm received (e.g., automatic, valve or manual).
      (4)   Recordkeeping.
         (A)   All records required to be maintained under this section shall be entered in a central station log which shall be maintained at each central station. The central station log shall be available at all times to the Department for inspection and copies shall be provided upon the Department's request. The central station log shall be kept on a yearly basis and be maintained for six (6) years following the period of use.
         (B)   The format of the central station log shall be either:
            (1)   a bound (not spiral bound) logbook for each calendar year, with consecutively numbered lined pages with entries made in ink;
            (2)   a computer database with a legend or key to all symbols and abbreviations; or
            (3)   any other format approved by the Commissioner. Where a computer format is used, the data may be stored on tape, disk or hard copy, provided that hard copies are maintained for 18 months following the period of use, in addition to the storage of the tape or disk for six (6) years following the period of use.
         (C)   A central station signaling system shall receive and retransmit all signals and information which the subscriber is required by law to transmit, such as the location of the alarm source (building, floor, section, zone, or subdivision) and/or the type of alarm signal (e.g., automatic, valve or manual). Central stations presently unable to determine the type of alarm signal received due to the lack of sufficient transmitters at the protected premises shall be granted a period of time, as the Department deems reasonable, to make the conversions necessary to comply with this requirement.
         (D)   Subsequent alarm and supervisory signals received from the same building shall be retransmitted to the Department upon receipt.
         (E)   A combination alarm signal that by its nature is indicative of waterflow in a sprinkler system at the protected premises shall be retransmitted in the same manner as a fire alarm signal. In addition, the designated representative for the protected premises shall be notified as soon as possible.
         (F)   The dates and times of the receipt and retransmission of all signals shall be recorded in the central station log.
      (5)   Runner service. A central station company shall ensure that a fire alarm system requiring manual silencing or resetting is restored to normal service no later than 90 minutes from receipt of an alarm signal. The central station company shall dispatch a runner to the protected premises for such purpose and shall immediately notify the Department once the system has been restored. A runner need not be dispatched and may be recalled if the central station confirms that the fire alarm system has already been restored, in which case the central station company shall immediately notify the Department of such fact.
      (6)   Notification of service disruptions.
         (A)   It is imperative that disruptions in central station service be detected as soon as possible and that service be restored immediately. The Department shall be notified of any disruption of fire alarm monitoring services regardless whether the disruption is due to failure of a fire alarm system, a fire suppression system, a protective signaling system, or central station equipment. The central station company shall make the following notifications:
            (1)   The central station company shall notify the Department whenever a fire alarm system or fire protection system is expected to be out of service for eight (8) hours or longer at a protected premises, where such information is available. This provision shall apply only to the installation of mandatory systems.
            (2)   The central station company must notify the Department and the designated representative for the protected premises forthwith in the event that a central station is either unable to receive alarm signals from a protected premises or to retransmit signals to the Department due to inoperative central station equipment or telephone circuitry. In making the above-described notifications, the central station company shall identify to the Department the terminal assignment number(s) for the affected premises, where such information is available.
         (B)   A central station company shall record in the central station log the following information relating to disruptions in service:
            (1)   All instances in which a fire alarm system or fire protection system is out of service for eight (8) hours or more at a protected premises, where such information is ascertainable. This record shall identify the terminal assignment number for the protected premises, as well as the date, time and duration of the disruption of service.
            (2)   All instances in which a protective signaling system at a protected premises is out of service for two (2) hours or more. This record shall identify the terminal assignment number for the protected premises, as well as the date, time and duration of the disruption in service.
      (7)   Posting of certificate. A copy of the certificate of operation shall be posted at each central station operated by the central station company.
   (g)   Compensation. Every central station company shall pay compensation to the Department in accordance with the provisions of 3 RCNY § 8104-01. Failure to timely remit such compensation shall be grounds for non-renewal, suspension or revocation of a certificate of operation, or denial of a new certificate of operation, in addition to any and all other remedies provided by law.
   (h)   Registration of Central Station-Monitored Fire Alarm Systems.
      (1)   Central station companies shall register each fire alarm system on each protected premises that it is monitoring by submitting to the Bureau of Fire Prevention, on the application form prescribed by the Department, the following information and such other information and documentation as the Department may require:
         (A)   The address of the protected premises in which the fire alarm system(s) are installed;
         (B)   The number and type of fire alarm systems monitored at the premises, regardless of the number of terminals associated with each such system;
         (C)   The floors, or portions thereof, monitored by each fire alarm system;
         (D)   The name, address and telephone number of the owner or operator of each fire alarm system; and
         (E)   The type and location of each terminal, including manual fire alarm boxes, sprinkler and standpipe system flow alarms and tamper switches, and heat, smoke and carbon monoxide detectors, associated with each fire alarm system.
      (2)   A central station company shall register with the Department each fire alarm system it proposes to monitor prior to the commencement of the receipt or retransmission of alarm signals from the fire alarm system, including resumption of previously discontinued or suspended monitoring service.
      (3)   The Department may deny a registration application upon a determination that the fire alarm system has not been installed and/or is not being operating in accordance with all applicable laws, rules and regulations, or other good cause. The Department may conduct an inspection of the protected premises to verify the proper installation and operation of the fire alarm system. A central station company shall not monitor any fire alarm system as to which the Department has denied registration.
      (4)   A central station company shall give prior written notice to the Department, on a form prescribed by the Department, of the discontinuance or temporary suspension of its monitoring of a fire alarm system, at least ten (10) days prior to such discontinuance or suspension. Five (5) additional days notice shall be provided if notice is given by mail.
      (5)   A central station company shall give written notice to the Department within seven (7) days of any change in any of the information set forth on its fire alarm system application form.
(Amended City Record 9/20/2023, eff. 10/20/2023)
§ 901-02 Maintenance of Sprinkler System Pressure Tanks.
   (a)   Scope. This section sets forth requirements for the periodic maintenance of pressure tanks that supply water to sprinkler systems.
   (b)   General Provisions. Water tanks that supply water to sprinkler systems shall be maintained in compliance with the requirements of FC 901.6, NFPA 25, and this section.
   (c)   Periodic Maintenance Requirements. Sprinkler system pressure tanks shall be inspected and tested at least monthly by a certificate of fitness holder and if necessary, corrective action taken, in accordance with the following procedure:
      (1)   Close both the top and bottom valves on the sight glass level gauge.
      (2)   Open the petcock at the bottom of the gauge glass and drain the water out of the glass by cracking the top valve to clear the glass. Close the petcock. Open the top valve and allow air to enter the glass.
      (3)   Open the bottom valve to allow water to enter the gauge glass. Open the top valve.
      (4)   When the air and water levels stabilize, the level should be at the 2/3 level or the level required for the design of the system. Immediate corrective action shall be taken in the event the water level is below the design level.
      (5)   If the water level is too high, drain water using the emergency valve on the tank. After draining to the design level, introduce compressed air into the tank until the design air pressure is obtained.
   (d)   Notification of Central Station. If the sprinkler system pressure tank is monitored by a central station, the central station company shall be notified before any testing is conducted.