When the proposed use is of equal or lesser hazard, further compliance with the code for new construction is not required, except as specified below:
(a) Exit signs and lights shall be provided, in accordance with Section 13-160-700.
(b) Means of egress lighting shall be provided, in accordance with Section 13-160-660.
(c) Fire alarm and extinguishing systems shall be provided, in accordance with Chapter 15-16.
(Prior code § 78.1-18)
When the proposed change in use results in an occupancy class one hazard index number higher than its present occupancy class as defined in Table 13-200-170, the entire building must meet all the requirements of the code for new construction, with the following exceptions:
(a) Existing stairways and elevators may remain but shall be upgraded by one of the following alternative methods:
(2) Noncombustible doors and assemblies shall be installed in the corridors between exit stairs. Such assemblies need not be rated but shall be constructed, as provided by Section 15-8-140(a).
(3) The entire building served by the existing stairs shall be provided with a standard sprinkler system, complying with the requirements of Chapter 15-16.
(Prior code § 78.1-19)
When the proposed change in use results in an occupancy class two or more hazard index numbers higher than its present occupancy class, as defined in Table 13-200-170, the entire building shall meet the requirements of Chapters 13-160, 15-8, 15-12 and 15-16, providing however that fire sprinklers shall not be required in any existing Type I building accommodating a day care center classified as a Type III school.
(Prior code § 78.1-20; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 4-16-96, p. 20112)
The allowance to increase the number of dwelling units under the provisions of this section shall apply to each building area separated by vertical separations providing fire resistance of not less than two hours and extending from the basement floor to the underside of the roof sheathing. All openings in such vertical separations shall be protected with Class B fire doors with self-closing devices.
(Prior code § 78.1-21)
As used in Sections 13-200-230, 13-200-240 and 13-200-300(d) of this chapter, the term “legally established dwelling units” shall mean the number of dwelling units authorized to exist in a residential building or a building of mixed occupancy, with one of the occupancies being residential, pursuant to the issuance of a valid building permit or authorized by a final and nonappealable court order.
(Prior code § 78.1-21(a); Added Coun. J. 10-28-87, p. 5549)
In any residential building or building of mixed occupancy, with one of the occupancies being residential, the number of dwelling units may be increased by one dwelling unit above the number of legally established dwelling units providing the building complies with the following requirements:
(a) The alterations meet the requirements of Title 17 of this Code;
(b) The building shall not be more than four stories high for ordinary construction (Types III-B or III-C), and not more than two stories high for combustible frame construction (Types IV-A or IV-B). Buildings of mixed ordinary and frame construction shall be governed by the requirements of combustible frame construction;
(c) A basement may be used for habitable rooms or a dwelling unit, regardless of the depth of the floor below grade, if the floors and walls are impervious to leakage of underground and surface runoff water and are protected against dampness, and if the required minimum window area is located entirely above the finished elevation of the ground adjoining the building wall in which the windows are located;
(d) Area and space requirements of Sections 13-196-470 through and including 13-196-490 shall be met in all rooms, except that at least 80 percent of the floor area of every habitable room shall have a ceiling height of not less than seven feet, six inches. Twenty percent of the floor area of any habitable room may have a ceiling height as low as six feet, eight inches;
(e) Natural Light and ventilation shall comply with requirements of Chapter 13-172;
(f) Exits shall comply with the exit requirements of Sections 13-200-330 through and including 13-200-360, except that basement dwelling units may have a second exit through a space containing a heating plant;
An existing building or structure may be increased in height or area up to the limits imposed by Chapter 13-48.
(g) If the basement contains a dwelling unit, the entire basement ceiling construction shall be one-half hour rated construction, or the original wood lath and plaster construction;
(h) Basement apartments shall be separated from heating plants as required by Section 15-8-190;
(i) Any subsequent or additional increase of one unit or more under this provision shall meet the requirements of Section 13-200-240.
(Prior code § 78.1-22; Amend Coun. J. 10-28-87, p. 5549; Amend Coun. J. 6-14-95, p. 2841; Amend Coun. J. 4-29-98, p. 66679, § 2)
Notes
Title 17 | The hyper-linked material is not part of the Chicago Building Code infobase and therefore is not included herein. The material is included in other provisions of the Chicago Municipal Code. The complete Chicago Municipal Code is available for purchase from American Legal Publishing in both print and Folio® versions. Please click here for the appropriate American Legal order form in printable Adobe® PDF format. For additional information, you may visit American Legal's website by clicking here. |
In any residential building or building of mixed occupancy with one of the occupancies being residential, the number of dwelling units may be increased by more than one dwelling unit above the number of legally established dwelling units providing the building complies with all of the requirements listed in Section 13-200-230, and also the following additional requirements:
(a) Stairways shall be enclosed with walls of one hour construction in buildings not exceeding three stories in height. Stairways shall be enclosed with walls of two hour construction if the building exceeds three stories in height. Stairwell enclosures may be combustible or noncombustible construction as long as the required separation ratings are met.
(b) Stairwell doors shall be one and three-fourths inches solid-core wood with one and three-fourths inches rabbeted wood frames in buildings not exceeding three stories in height. Stairwell doors shall be Class B and frames in buildings exceeding three stories in height. All stair doors shall be self-closing.
(c) All existing dwelling and corridor separations shall be one-half-hour rated construction, combustible or noncombustible. All new dwelling and corridor separations shall be one hour rated construction, combustible, or noncombustible.
(d) Corridor doors to dwelling units shall be one and three-fourths inches solid core wood with one and three-fourths inches rabbeted wood frames. All corridor doors to dwelling units shall be self-closing.
(e) Heating plant enclosures shall comply with the requirements of Section 15-8-190.
(f) Basement ceilings shall comply with the requirements of Section 13-60-200.
(Prior code § 78.1-23; Amend Coun. J. 10-28-87, p. 5549)
An existing building or structure may be increased in height or area up to the limits imposed by Chapter 13-48.
(a) When the floor area is increased by not more than 25 percent of the original building, only the new construction need conform to all requirements of this Code for new construction. When the floor area is increased by more than 25 percent of the original building, the entire building shall conform to all requirements of this Code.
(b) Where a fire wall complying with Chapter 15-8 is provided which separates the addition from the existing building, only the new construction need conform to all requirements of this Code for new construction, regardless of the percentage increase in area created by the addition. Such an addition with the required fire wall separation, may also be considered a separate building if on a separate lot.
(c) No addition shall impose exiting loads which exceed the capacity of the existing building exits without provision of additional exits, in conformance with Section 13-200-330 through and including 13-200-360 of this chapter for the existing building or Chapter 13-160 for the addition.
(d) No addition shall impose structural loads, either vertical or horizontal, which would cause the existing building to be subjected to stresses exceeding those permitted by the new construction. Any increase in floor or roof loading shall be investigated to determine the adequacy of the existing floor system to support the increased loads. If the existing floor system is found to be inadequate, it shall be modified to support the increased loads.
(Prior code § 78.1-24; Amend Coun. J. 2-13-85, p. 13525)