Every public utility structure (as defined in Section 13-96-1080) and every technology center (as defined in Section 13-56-121) hereafter erected, and every existing public utility structure which repairs or alterations are made within a 12-month period to 50 percent or more of the electrical equipment contained therein, shall be provided with either a standard sprinkler system or a non-water based extinguishing system that complies with the requirements of Chapter 15-16. The type of fire suppression system installed in a public utility structure or technology center shall be indicated on a sign installed and prominently visible at the entrance to the structure. If a building is protected in whole or in part by a non-water based extinguishing system in lieu of a standard sprinkler system, the bonuses provided in this Code for installation of a standard sprinkler system shall not apply.
(Added Coun. J. 11-2-94, p. 58476; Amend Coun. J. 6-28-00, p. 36679, § 7; Amend Coun. J. 11-8-12, p. 38872, § 233)