Skip to code content (skip section selection)
Compare to:

You are viewing an archived code

15-16-050  Highly flammable material storage.
   Automatic sprinkler protection shall be required in every such room as required in Section 15-28-620. Such sprinkler system shall be so designed that the floor area covered by each sprinkler head shall not exceed 100 square feet. If piling of bales or loose highly flammable material exceeds 12 feet, such sprinkler system shall be hydraulically designed to provide a density of .20 to .30 gallons per minute per square foot over the maximum floor area which would be involved.
(Prior code §  64-5)