15-28-730  Storage or baling of wastepaper.
   Every room designed, intended or used for the storage or baling of wastepaper in a building of Type IA, IB, IC or II construction shall have an enclosure of not less than two-hour fire-resistive construction with every doorway in such an enclosure having a Class B fire door and every window therein a fire window. Every such room in a building of Type IIIA, IIIB or IIIC construction shall have walls and ceiling of not less than one-hour fire-resistive construction with every doorway in such an enclosure having a Class C fire door.
(Prior code §  92-62)