Skip to code content (skip section selection)
Compare to:
Chicago Overview
Prior Chicago Building Code
BUILDING CODE AND RELATED EXCERPTS OF THE MUNICIPAL CODE OF CHICAGO
DIVISION 1 - ADMINISTRATION
DIVISION 2 - DEFINITIONS
DIVISION 3 - USE AND OCCUPANCY CLASSIFICATIONS
DIVISION 4 - SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY
Subdivision 403 - High-Rise buildings
Subdivision 406 - Motor-Vehicle-Related Occupancies
Subdivision 407 - Special Institutional
Subdivision 411 - Special Amusement Buildings
Subdivision 413 - Combustible Storage
Subdivision 414 - Hazardous Materials
Subdivision 421 - Special Detailed Requirements
DIVISION 5 - GENERAL BUILDING HEIGHTS AND AREAS
DIVISION 6 - TYPES OF CONSTRUCTION
DIVISION 7 - FIRE-RESISTANCE-RATED CONSTRUCTION
DIVISION 8 - INTERIOR FINISHES (NA)
DIVISION 9 - FIRE PROTECTION SYSTEMS
DIVISION 10 - MEANS OF EGRESS
DIVISION 11 - ACCESSIBILITY
DIVISION 12 - INTERIOR ENVIRONMENT
DIVISION 13 - ENERGY EFFICIENCY AND ENVIRONMENTAL PROTECTION
DIVISION 14 - EXTERIOR WALLS (NA)
DIVISION 15 - ROOF ASSEMBLIES AND ROOFTOP STRUCTURES (NA)
DIVISION 16 - STRUCTURAL DESIGN
DIVISION 17 - STRUCTURAL TESTS AND SPECIAL INSPECTIONS
DIVISION 18 - SOILS AND FOUNDATIONS
DIVISION 19 - CONCRETE
DIVISION 20 - ALUMINUM (NA)
DIVISION 21 - MASONRY
DIVISION 22 - STEEL
DIVISION 23 - WOOD
DIVISION 24 - GLASS AND GLAZING (NA)
DIVISION 25 - GYPSUM BOARD AND PLASTER (NA)
DIVISION 26 - PLASTIC (NA)
DIVISION 27 - ELECTRICAL
DIVISION 28 - MECHANICAL SYSTEMS
DIVISION 29 - PLUMBING SYSTEMS
DIVISION 30 - ELEVATORS AND CONVEYING SYSTEMS
DIVISION 31 - SPECIAL CONSTRUCTION (NA)
DIVISION 32 - ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
DIVISION 33 - SAFEGUARDS DURING CONSTRUCTION
DIVISION 34 - EXISTING STRUCTURES
DIVISION 35 - REFERENCED STANDARDS

You are viewing an archived code

Loading...
15-28-210  Safety clearances.
   No oxidizing material building shall be located nearer than 100 feet to any building in which there is an institutional, assembly or open air assembly unit, except as otherwise provided.
(Prior code §  92-16)
15-28-220  Fire prevention requirements.
   The storage and handling of oxidizing materials other than that used for retail sales in original sealed containers, located in mercantile units as defined in Section 13-56-130, shall comply with the following requirements:
   (1)   Quantities in excess of one day's supply shall be stored in buildings or rooms conforming to the requirements for hazardous chemicals. The user shall notify the fire commissioner by notarized letter of the amount used in one day. Upon any change in that amount, the fire commissioner shall be notified within 24 hours.
   (2)   The use of oxidizing materials in buildings shall be limited to use in rooms complying with the requirements for hazardous chemical rooms.
   (3)   Oxidizing materials shall be stored in dry locations and shall be separated from organic materials by walls conforming to the requirements of hazardous chemicals rooms.
   (4)   Bulk oxidizing materials shall not be stored on or against wooden surfaces.
   (5)   Defective containers which permit leakage or spillage shall be disposed of or repaired in an approved manner. No spilled materials shall be allowed to accumulate on floors or shelves.
   (6)   Signs having a white field with red letters four inches high and having a one-half-inch stroke shall be conspicuously posted. Such signs shall read “Oxidizing Materials – Keep Fire Away”.
   (7)   Tanks, which contain more than 55 gallons of oxidizing materials, shall be located outside of any building or buried below ground level. When aboveground, said tank or tanks containing liquids, shall be diked. Each dike shall have a capacity of not less than one and one-half times the combined capacity of the tank or tanks it surrounds. Dike construction shall be as specified in Section 15-24-170 of this Code; provided, however, the material of the dike walls shall be inert with respect to the materials contained within the tank or tanks.
   (8)   The provisions of this section shall apply to all existing as well as newly installed tanks. All tanks, piping and fittings shall be compatible with the material to be stored or handled. Outlets and inlets of all aboveground tanks shall have a shutoff valve as close as possible to the tank, with no branches or outlets between the tank and valve. All inlet pipes shall have an additional check valve as close as possible to the tank valve. In addition to any other valves when the material stored is reactive with air or water, there shall be a valve at each pipeline connection to any tank below the liquid level which valve shall be effective inside the tank shell or head and can be operated manually to prevent the flow of liquid from the tank even though the pipelines are broken from the tank. All remote reach rods to valves shall be of substantial construction and shall be accessibly located and clearly marked “Emergency Shutoff Valve”. There shall be an effective flexible connection between that tank valve and piping system or the piping shall be so arranged with swing joints to prevent stress and strain between the piping system and tank. Where the exterior piping and sides of the tank are not inert to the material being stored, the piping supports and tank shall be made inert by coating or some other means to one and one-half times the height of the dike.
   (9)   Tanks or tank cars of oxidizing materials of any capacity shall not be located within one-eighth mile from any school, institutional unit, multiple dwelling or place of public assembly.
   (10)   Whenever an oxidizing material can be chemically changed to a less dangerous and more stable material, a qualified chemist of the manufacturer shall state in writing the safest and quickest method of changing the total capacity of the tank or tanks in case of a rupture, spillage or other emergency. The owner and/or operator of said tank or tanks shall keep sufficient quantities of the changing agent as hereinbefore determined so as to be readily available in the event of emergency.
   (11)   The name and address of the manufacturer or the nearest producer of the specific oxidizing material being used and a placard outlining emergency first aid directions shall be posted and remain posted in a conspicuous place at the points of unloading and use and in at least one other approved location.
   Oxygen-generating or self-contained air or oxygen masks having a United States Bureau of Mines or National Institute of Occupational Safety and Health approval for a minimum of one-half hour protection shall be maintained in a readily accessible location, outside the areas of probable contamination and sufficient for all personnel associated with the operation.
   Additional air or oxygen containers which will provide for a minimum of one-hour use of each mask shall be kept at the location of each gas mask. All personnel that may be required to use gas masks must be required at reasonable intervals to practice their application and use. Gas masks must be kept in condition, ready for immediate use at all times with fully charged containers.
   An approved repair kit with all the necessary tools, appurtenances and material required to repair a leak or replace a defective valve or other part, shall be kept in a location accessible to the tank car and outside the probable area of contamination.
   Protective clothing suitable for use with the materials stored shall be provided and be kept in good condition where its use will provide effective protection against the oxidizing material.
   Gas masks, repair kit and duplicate wrenches shall be kept in a conspicuous location and shall be conspicuously labeled for immediate identification.
(Prior code § 92-17; Amend Coun. J. 5-18-16, p. 24131, § 154)
ARTICLE IV.  NITROMETHANE (15-28-230 et seq.)
15-28-230  Storage requirements.
   Nitromethane shall be stored only in outside storage areas in original drums. Such areas shall be equipped with a deluge-type automatic sprinkler system as directed in Chapter 15-16 unless provided with the minimum safety clearances specified in Section 15-28-250. Nothing in this chapter shall be construed as prohibiting the storage of nitromethane in underground tanks, installed in underground tanks complying with the requirements of Section 15-24-280. Nothing in this section shall be construed as prohibiting the storage of nitromethane in aboveground tanks complying with the requirements of Section 15-24-170 with safety clearances complying with Section 15-28-250 as given below.
(Prior code §  92-18)
15-28-240  Storage prohibited in buildings.
   The storage and handling of nitromethane shall comply with the following requirements:
   (1)   Nitromethane shall not be stored in any building. Such nitromethane shall be stored in outside storage areas complying with the requirements below.
   (2)   The amount of nitromethane brought into any building shall be limited to that required for immediate use.
(Prior code §  92-19)