Heating in rooms and buildings used for the storage and handling of Class I flammable liquids shall be by steam, hot water or approved electrical heaters installed in accordance with Title 14E. Fire walls shall surround all boilerrooms, furnace rooms and other rooms containing exposed fire, electric dynamos, motors, switches or other spark-producing devices.
(Prior code § 129.1-5; Amend Coun. J. 9-6-17, p. 55278, Art. II, § 52)
For oily rags and waste disposal, see Section 15-4-960 of this Code.
(Prior code § 129.1-8; Amend Coun. J. 6-14-95, p. 2841)
For sewer restrictions, see Section 13-168 -940 of this Code.
(Prior code § 129.1-9)
Notes
13-168 | The hyper-linked material is not part of the Chicago Building Code infobase and therefore is not included herein. The material is included in other provisions of the Chicago Municipal Code. The complete Chicago Municipal Code is available for purchase from American Legal Publishing in both print and Folio® versions. Please click here for the appropriate American Legal order form in printable Adobe® PDF format. For additional information, you may visit American Legal's website by clicking here. |