15-24-070  Drains.
   There shall be no floor drains or other connections to the city sewer system from a tank or tank manhole or any room or compartment in which flammable liquids are stored or used, except where fuel oil is stored having a capacity of 550 gallons or less.
(Prior code §  129.1-5.1)
15-24-080  Use for illumination prohibited.
   No system of artificial lighting and no lamp, torch or other device for illumination, which employs any Class I flammable liquid shall be installed in any new or existing building.
(Prior code §  129.1-6)
15-24-090  Portable appliances.
   It shall be unlawful to use gasoline stoves, portable gasoline lamps, gravity gasoline torches, or stoves inside of any completed building in the city.
(Prior code §  129.1-7)
15-24-100  Oily rags and waste.
   For oily rags and waste disposal, see Section 15-4-960 of this Code.
(Prior code §  129.1-8; Amend Coun. J. 6-14-95, p. 2841)
15-24-110  Discharge into sewers.
   For sewer restrictions, see Section 13-168 -940 of this Code.
(Prior code §  129.1-9)

 

Notes

13-168
The hyper-linked material is not part of the Chicago Building Code infobase and therefore is not included herein.  The material is included in other provisions of the Chicago Municipal Code.  The complete Chicago Municipal Code is available for purchase from American Legal Publishing in both print and Folio® versions.  Please click here for the appropriate American Legal order form in printable Adobe® PDF format.  For additional information, you may visit American Legal's website by clicking here.
15-24-120  Workmen's clothes lockers.
   For workmen's clothes locker requirements, see Section 15-4-980 of the code.
(Prior code §  129.1-10)
15-24-130  Grounding of equipment.
   All moving equipment, metal floors and railings, pumps, motors and machinery, in a hazardous use unit used for explosive hazard materials shall be permanently and safely grounded to guard against static electricity sparks.
(Prior code §  129.1-11)
15-24-140  Electrical equipment.
   Explosion-Proof Motors. When electric motors are required in any room containing explosive or flammable vapor or atmosphere, such motors shall be of types approved, for use in hazardous locations, as required by the electrical regulations of this Code.
   Other Motors. Any electrical motor, other than an explosion-proof motor, shall be located in a separate building, or separated by a standard fire wall from any room or hazardous use unit containing explosive or flammable vapor or atmosphere.
   Switches and Control Devices. Every electric switch or other control device in any room required by the first paragraph to have explosion-proof motors, shall be of a type approved for use in the presence of explosive or flammable vapor or atmosphere.
(Prior code §  129.1-12)