The owner, operator or manager of a temporary overnight shelter may allow the use of smoking materials therein, but only in an area separated from sleeping areas and under supervision of the staff of the shelter. No person shall use smoking materials in any sleeping area of a shelter.
(Prior code § 78.4-12; Added Coun. J. 12-22-83, p. 4214)
Approved smoke alarms, as described in Section 13-64-150, shall be installed and maintained in the manner designated in said chapter, in each temporary overnight shelter, as follows:
(a) Within each sleeping area;
(b) In each corridor, with the distance between smoke detectors not to exceed 40 feet;
(c) At the uppermost ceiling of each stairwell and open shaft; and
(d) In each room or area used for storage.
(Prior code § 78.4-13; Added Coun. J. 12-22-83, p. 4214; Amend Coun. J. 9-6-17, p. 55278, Art. VI, § 34)
If a temporary overnight shelter is operated in a building classified as a mixed occupancy in accordance with Section 13-56-240 of this Code, the shelter shall be separated from each adjoining occupancy in the manner prescribed in Section 13-56-280, except that separations between a shelter and any occupancies classified as C-1, C-2, C-3, E or F may be reduced to one hour; openings in such separations shall be protected by doors, frames, and closers of at least Class B, as described in Section 15-12-110 of this Code. Provisions of Section 13-64-020(c) of this Code shall not apply to temporary overnight shelters.
(Prior code § 78.4-16; Added Coun. J. 12-22-83, p. 4214; Amend Coun. J. 10-15-87, p. 4811)
Standard fire extinguishers shall be installed and maintained in each temporary overnight shelter as required by Chapter 15-16 of this Code.
(Prior code § 78.4-17; Added Coun. J. 12-22-83, p. 4214)
Each temporary overnight shelter shall provide a minimum of one water closet for each 15 persons or fraction thereof of its maximum capacity (including staff), but in no event less than one water closet. If a shelter has a capacity of 30 or more occupants (excluding staff), at least one bathtub or shower shall be provided. Except as otherwise stated herein, temporary overnight shelters shall be subject to the sanitation requirements established by Chapter 18-29 of this Code.
(Prior code § 78.4-18; Added Coun. J. 12-22-83, p. 4214; Amend Coun. J. 11-9-16, p. 36266, § 29)
The sleeping areas of each temporary overnight shelter shall meet the ventilation requirements for sleeping stall rooms, established by Chapter 18-29 of this Code.
(Prior code § 78.4-19; Added Coun. J. 12-22-83, p. 4214; Amend Coun. J. 11-9-16, p. 36266, § 29)