Approved smoke alarms, as described in Section 13-64-150, shall be installed and maintained in the manner designated in said chapter, in each temporary overnight shelter, as follows:
(a) Within each sleeping area;
(b) In each corridor, with the distance between smoke detectors not to exceed 40 feet;
(c) At the uppermost ceiling of each stairwell and open shaft; and
(d) In each room or area used for storage.
(Prior code § 78.4-13; Added Coun. J. 12-22-83, p. 4214; Amend Coun. J. 9-6-17, p. 55278, Art. VI, § 34)