§ 156.053 FIRE HYDRANTS AND FIRE DEPARTMENT ACCESS.
   (A)   All streets and any secondary access roads shall have an unobstructed width of 20 feet with a minimum vertical clearance of 13 6.
   (B)   All houses in the subdivision shall have proper house numbers identifying the correct street address as specified by the 911 Committee.
   (C)   Fire hydrants shall be installed so that the maximum distance from any fire hydrant shall not exceed 500 feet as measured along the roadway. The location and spacing of the hydrants shall be approved by the Fire Chief of the city.
   (D)   All fire hydrants shall be supplied by a minimum of a six inch diameter water main.
   (E)   Hydrants shall be Mueller A-421 LEFT - 3½ feet bury or approved equal.
   (F)   Fences, trees, signs, or landscaping will not be installed so as to obstruct or screen fire hydrants.
(Ord., passed 10-13-92; Am. Ord. 07-019, passed 8-14-07) Penalty, see § 156.999