D103.5 Fire Apparatus Access Road Gates.
Amend item 5 as follows:
5. Electric gates shall be equipped with an automatic opening mechanism activated by the Opticom system currently in use by the fire department and a Knox key switch. A stand-alone Knox key switch may be used in place of an Opticom system when approved by the Fire Code Official.
Add item 9 as follows:
9. Electric gates shall be of a fail-open version in the event of loss of power.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
D107.1 One- or Two-Family Dwelling Residential Developments. Amend Exception 1 to read as follows:
1. Where there are less than 60 dwelling units on a single public or private fire apparatus access road and all dwelling units are equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3 of the International Fire Code, access from two directions shall not be required.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)