Loading...
903.3.5.3 Control Valve Location. Fire sprinkler system main control valves shall be located in a fire sprinkler riser room that is separated from the building on all sides by a one-hour fire barrier, horizontal assembly, or both, including opening and penetration protection, as defined by the Building Code. The fire sprinkler riser room shall be provided with an exterior door that opens directly into the room.
Exception: Sprinkler systems provided with post indicator valves located in an approved location.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 10-23, 3-7-2023)
903.4.3 Floor Control Assembly. Unless otherwise approved by the fire code official, supervised floor control assemblies shall be provided at the point of connection on each floor in buildings four (4) or more stories in height.
Exceptions:
1. One- and two-family dwellings.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 10-23, 3-7-2023)
904.7.2 Use of Foam-Water Suppression Systems. Only UL listed fluorine-free foam shall be used for the installation or modification of a foam-water suppression system. Proper disposal shall be provided for the fluorine foam being replaced as approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 7-25, 2-25-2025)
906.5.1 Multi-Story Installation Near Stairwells. In multi-story buildings, at least one 2A fire extinguisher shall be located adjacent to the stairway at each floor level. Extinguishers shall not be placed on half landings unless approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
907.6.6.3 Single Communication Path Monitoring Systems. IP based single communication path monitoring systems are prohibited unless approved by the Fire Marshal prior to submittal for permit. Approval shall only be permitted when, in the opinion of the fire code official, no reasonable alternative exists.
(Ord. 7-25, 2-25-2025)
907.6.7 FACP Location and Identification. The fire alarm control panel (FACP) shall be mounted in such a location to be in obvious view from the main entrance of the building.
Exception: When the FACP is not in obvious view, a remote annunciator shall be provided at the main entrance of the building and approved signage shall be installed to indicate the location of the FACP.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
912.2.3 Distance to Access and Water Supply. Fire department connections (FDC's) and associated outside alarm indicator shall be installed within 100 feet of an approved fire apparatus access lane and within 300 feet of a fire hydrant.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
914.3.1.2 Water supply to required fire pumps. In all buildings that are more than 420 feet (128 m) in building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet (36.6 m) in building height, required fire pumps shall be supplied by connections to not fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate.
Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections.
(Ord. 50-21, 11-30-2021, eff. 1-1-2022)
914.8.3.3 Use of Foam Systems in Aircraft Hangars
Only UL listed flourine-free foam shall be used for the installation or modification of a foam-water suppression system. Proper disposal shall be provided for the flourine foam being replaced as approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 7-25, 2-25-2025)
1101.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code, if in the opinion of the fire code official they constitute a distinct hazard to life or property.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
Section 2007.6 Foam Protection. Add a paragraph to the end of 2007.6 to read as follows: Prior to the approval of any permit for the installation or modification of a foam-water suppression system, approval in writing shall be received from the fire code official. Approval shall only be permitted when in the opinion of the fire code official no reasonable alternative to these systems exist. Where permitted, mitigation measures shall be provided as approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
3304.5 Fire Watch. Add a paragraph to the end of 3304.5 to read as follows:
Where approved by the fire code official, a fire watch may be used to permit the temporary occupancy of a building before it is completed or during demolition.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
3304.9 Fire safety requirements for buildings of Types IV-A, IV-B and IV-C construction. Buildings of Types IV-A, IV-B and IV-C construction designed to be greater than six stories above grade plane shall comply with the following requirements during construction unless otherwise approved by the fire code official.
1. Standpipes shall be provided in accordance with Section 3314.
2. A water supply for fire department operations, as approved by the fire code official and the fire chief.
3. Where building construction exceeds six stories above grade plane and noncombustible protection is required by Section 602.4 of the International Building Code, at least one layer of noncombustible protection shall be installed on all building elements on floor levels, including mezzanines, more than four levels below active mass timber construction before additional floor levels can be erected.
Exception: Shafts and vertical exit enclosures shall not be considered part of the active mass timber construction.
4. Where building construction exceeds six stories above grade plane, required exterior wall coverings shall be installed on all floor levels, including mezzanines, more than four levels below active mass timber construction before additional floor levels can be erected.
Exception: Shafts and vertical exit enclosure shall not be considered part of the active mass timber construction.
(Ord. 50-21, 11-30-2021, eff. 1-1-2022)
4001 GENERAL. This chapter shall apply to new and existing childcare facilities including Family Childcare Homes, Group Childcare Homes and Childcare Centers. All other maintenance and construction provisions of this code for general or specific occupancies or hazards shall also apply.
4002 EXISTING FACILITIES. Childcare facilities legally approved, and in existence prior to adoption of this code, shall comply with the code under which they were approved. Maintenance provisions of this chapter shall apply to existing facilities. Facilities that cease to operate for a period of six (6) months or more, and are seeking a new license, shall be considered a new childcare facility.
4003 LICENSE AND INSPECTION. Each premise shall be inspected as often as is deemed necessary by the fire code official or the City Clerk. The City Clerk shall inspect, or cause to be inspected, all Family or Group Childcare Homes before granting a license to operate. The fire code official shall inspect, or shall cause to have inspected, all other Childcare facilities before the City Clerk grants a license to operate.
4004 LOCATION OF FACILITIES. Facilities or portions of facilities located on a story below the level of exit discharge shall have at least two (2) exits which must open directly to the exterior, one (1) of which shall exit directly from the basement to the exterior. Facilities shall not be located more than one (1) story below ground level. Facilities or portions of facilities located on a story above the level of exit discharge shall have at least two (2) exits which must open directly to the exterior and shall be protected with an automatic fire sprinkler system.
4005 EXITS. Exits in childcare facilities shall comply with the International Fire Code.
4005.1 Sliding Door. In Family Childcare Homes and Group Childcare Homes, a sliding door is acceptable as a second exit provided there is also a primary entry/exit door meeting the International Residential Code requirements for dwellings.
4006 SAFETY. Childcare facilities shall meet all of the following safety requirements.
4006.1 Closet Doors. Every closet door latch shall be such that children can open the door from inside the closet.
4006.2 Bathroom Doors. Every bathroom door lock shall permit opening of the locked door from outside in the event of an emergency. The opening device shall be readily accessible to the staff.
4006.3 Receptacle Covers. All electrical outlets not in immediate use shall be provided with receptacle covers or approved safety devices.
4006.4 Flashlights. Childcare facilities, with an occupant load of less than 50, shall have at least one (1) flashlight immediately available for each member of the staff.
4006.5 Portable Fire Extinguishers. A minimum of one (1) 2A-10BC portable fire extinguisher shall be provided on each floor of childcare facilities. Travel distance to portable fire extinguishers shall not exceed seventy-five (75) feet.
4007 SMOKE ALARMS. Smoke alarms shall be installed in the following locations:
1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of sleeping rooms.
2. In each room used for sleeping, lounging or recreation purposes.
3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics.
4. At the top and bottom of the stairways and at no greater spacing than 30 feet on center throughout the corridors of all floors.
Exception: A childcare Facility not provided with sleeping facilities that only provides care for children more than six (6) years of age.
4007.1 Power Source. In new facilities, required smoke alarms shall receive their primary power from the building wiring, where such wiring is served from a commercial source, and shall be equipped with a battery backup.
4008 TESTING AND MAINTENANCE. Operators of childcare facilities shall maintain, in working order, all fire and life safety equipment, systems, and facilities. Inspection, testing and maintenance shall be performed in accordance with this section and other provisions of this code.
4008.1 Monthly. The following items shall be completed monthly:
1. Manual fire alarm system test;
2. Testing of all smoke alarms;
3. Visual inspection of all portable fire extinguishers;
4. Testing all emergency lighting and flashlights for proper operation.
4008.2 Biannual. The following items shall be completed every six (6) months:
1. Replace the batteries of all battery powered smoke alarms with new batteries;
2. Replace the batteries in all flashlights with new batteries.
4008.3 Records. A record of all required inspections, tests and repairs shall be kept on the premises and be made available at the time of license inspection.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
Loading...