903.3.5.3 Control Valve Location. Fire sprinkler system main control valves shall be located in a fire sprinkler riser room that is separated from the building on all sides by a one-hour fire barrier, horizontal assembly, or both, including opening and penetration protection, as defined by the Building Code. The fire sprinkler riser room shall be provided with an exterior door that opens directly into the room.
Exception: Sprinkler systems provided with post indicator valves located in an approved location.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 10-23, 3-7-2023)
903.4.3 Floor Control Assembly. Unless otherwise approved by the fire code official, supervised floor control assemblies shall be provided at the point of connection on each floor in buildings four (4) or more stories in height.
Exceptions:
1. One- and two-family dwellings.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 10-23, 3-7-2023)
904.7.2 Use of Foam-Water Suppression Systems. Only UL listed fluorine-free foam shall be used for the installation or modification of a foam-water suppression system. Proper disposal shall be provided for the fluorine foam being replaced as approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 7-25, 2-25-2025)
906.5.1 Multi-Story Installation Near Stairwells. In multi-story buildings, at least one 2A fire extinguisher shall be located adjacent to the stairway at each floor level. Extinguishers shall not be placed on half landings unless approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
907.6.6.3 Single Communication Path Monitoring Systems. IP based single communication path monitoring systems are prohibited unless approved by the Fire Marshal prior to submittal for permit. Approval shall only be permitted when, in the opinion of the fire code official, no reasonable alternative exists.
(Ord. 7-25, 2-25-2025)