906.5.1 Multi-Story Installation Near Stairwells. In multi-story buildings, at least one 2A fire extinguisher shall be located adjacent to the stairway at each floor level. Extinguishers shall not be placed on half landings unless approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
907.6.6.3 Single Communication Path Monitoring Systems. IP based single communication path monitoring systems are prohibited unless approved by the Fire Marshal prior to submittal for permit. Approval shall only be permitted when, in the opinion of the fire code official, no reasonable alternative exists.
(Ord. 7-25, 2-25-2025)
907.6.7 FACP Location and Identification. The fire alarm control panel (FACP) shall be mounted in such a location to be in obvious view from the main entrance of the building.
Exception: When the FACP is not in obvious view, a remote annunciator shall be provided at the main entrance of the building and approved signage shall be installed to indicate the location of the FACP.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
912.2.3 Distance to Access and Water Supply. Fire department connections (FDC's) and associated outside alarm indicator shall be installed within 100 feet of an approved fire apparatus access lane and within 300 feet of a fire hydrant.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)
914.3.1.2 Water supply to required fire pumps. In all buildings that are more than 420 feet (128 m) in building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet (36.6 m) in building height, required fire pumps shall be supplied by connections to not fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate.
Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections.
(Ord. 50-21, 11-30-2021, eff. 1-1-2022)
914.8.3.3 Use of Foam Systems in Aircraft Hangars
Only UL listed flourine-free foam shall be used for the installation or modification of a foam-water suppression system. Proper disposal shall be provided for the flourine foam being replaced as approved by the fire code official.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021; amd. Ord. 7-25, 2-25-2025)
1101.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code, if in the opinion of the fire code official they constitute a distinct hazard to life or property.
(Ord. 48-20, 12-8-2020, eff. 1-1-2021)