SECTION P-917 SINGLE-STACK VENT SYSTEM
* * *
P-917.6 Additional venting required. Additional venting shall be provided where more than one water closet discharges to a horizontal branch and where the distance from a fixture trap to the stack exceeds the limits in Section 917.4. Where additional venting is required, the fixture(s) shall be vented by individual vents, common vents, wet vents, circuit vents, or a combination waste and vent pipe. The dry vent extensions for the additional venting shall connect to a branch vent, vent stack, stack vent, air admittance valve, or shall terminate outdoors.  399
* * *

 

Notes

399
   Amended, Bill No. 230653 (approved December 20, 2023), effective April 1, 2024.