P-308.3 Materials. Hangers, anchors and supports shall support the piping and the contents of the piping. Hangers and strapping material shall be of approved material that will not promote galvanic action. 347
* * *
PIPING MATERIAL
|
MAXIMUM HORIZONTAL SPACING (feet)
|
MAXIMUM VERTICAL SPACING (feet) |
PIPING MATERIAL
|
MAXIMUM HORIZONTAL SPACING (feet)
|
MAXIMUM VERTICAL SPACING (feet) |
Acrylonitrile butadiene styrene (ABS) pipe | 4
c | 10
b |
Aluminum tubing |
10 | 15 |
Brass pipe |
10 | 10 |
Cast-iron pipe | 5
a |
15 |
Chlorinated polyvinyl chloride (CPVC) pipe and tubing, 1 inch and smaller |
3 | 10
b |
Chlorinated polyvinyl chloride (CPVC) pipe and tubing, 1-1/4 inches and larger | 4c | 10
b |
Copper or copper-alloy pipe |
12 | 10 |
Copper or copper-alloy tubing, 1-1/4 inch diameter and smaller |
6 | 10 |
Copper or copper-alloy tubing, 1-1/2 inch diameter and larger |
10 | 10 |
Cross-linked polyethylene (PEX) pipe 1 inch and smaller |
2.67 (32 inches) | 10
b |
Cross-linked polyethylene (PEX) pipe 1-1/4 inch and larger | 4c | 10
b |
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe |
2.67 (32 inches) | 4 |
Lead pipe |
Continuous | 4 |
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe |
2.67 (32 inches) | 4 |
Polyethylene of raised temperature (PE-RT) pipe 1 inch and smaller |
2.67 (32 inches) | 10
b |
Polyethylene of raised temperature (PE-RT) pipe 1-1/4 inch and larger | 4c | 10
b |
Polypropylene (PP) pipe or tubing 1 inch and smaller |
2.67 (32 inches) | 10
b |
Polypropylene (PP) pipe or tubing, 1-1/4 inches and larger | 4
c | 10
b |
Polyvinyl chloride (PVC) pipe | 4
c | 10
b |
Stainless steel drainage systems |
10 | 10
b |
Steel pipe |
12 | 15 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
b. For sizes 2 inches and smaller, a guide shall be installed midway between required vertical supports. Such guides shall prevent pipe movement in a direction perpendicular to the axis of the pipe.
c. The maximum horizontal spacing of hangers shall be decreased to 3 feet where temperatures exceed 120 degrees Fahrenheit.
* * *
Notes
347 | Amended,
Bill No. 230653 (approved December 20, 2023), effective April 1, 2024. |