SECTION M1602  RETURN AIR
Pursuant to the UCC, delete Section M1602.2 and replace as follows:
R-M1602.2 Return air openings. Return air openings for heating, ventilation and air conditioning systems shall comply with all of the following:
   1.   Openings shall not be located less than 10 feet (3048 mm) measured in any direction from an open combustion chamber or draft hood of another appliance located in the same room or space.
   2.   The amount of return air taken from any perimeter room or space shall be not greater than the flow rate of supply air delivered to such room or space.
   3.   Return and transfer openings shall be sized in accordance with the appliance or equipment manufacturers' installation instructions, Manual D or the design of the registered design professional.
   4.   Return air shall not be taken from a closet, bathroom, toilet room, kitchen, garage, mechanical room, boiler room, furnace room or unconditioned attic.
   Exceptions:
      1.   Taking return air from a kitchen is not prohibited where such return air openings serve the kitchen only, and are located not less than 10 feet (3048 mm) from the cooking appliances.
      2.   Dedicated forced-air systems serving only the garage shall not be prohibited from obtaining return air from the garage.
      3.   Taking return air from an unconditioned crawl space shall not be accomplished through a direct connection to the return side of a forced-air furnace. Transfer openings in the crawl space enclosure shall not be prohibited.
      4.   Return air from one dwelling unit shall not be discharged into another dwelling unit.