1017.1 General.
Travel distance within the exit access portion of the means of egress system shall be in accordance with this section.
1017.2 Limitations.
Exit access travel distance shall not exceed the values given in Table 1017.2.
Occupancy | Without Sprinkler System (feet) | With Sprinkler System (feet) |
Occupancy | Without Sprinkler System (feet) | With Sprinkler System (feet) |
A | See Section 1029.7 | |
E, F-1, M, R, S-1 | 150 | 200
b |
B | 200 | 300
c |
F-2, S-2, U | 200 | 250
c |
H-1 | Not Permitted | 75
d |
H-2 | Not Permitted | 100
d |
H-3 | Not Permitted | 150
d |
H-4 | Not Permitted | 175
d |
H-5 | Not Permitted | 200
c |
I-1, I-2, I-3, I-4 | Not Permitted | 200
c |
For SI: 1 foot = 304.8 mm
a. See the following sections for modifications to exit access travel distance requirements:
Section 402.8: For the distance limitation in malls.
Section 404.9: For the distance limitation through an atrium space.
Section 407.4: For the distance limitation in Group I-2.
Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3.
Section 411.4: For the distance limitation in special amusement buildings.
Section 412.7: For the distance limitations in aircraft manufacturing facilities.
Section 407.4.2: For the distance limitation in Group I-2 hospital suites.
Section 1006.2.2.2: For the distance limitation in refrigeration machinery rooms.
Section 1006.2.2.3: For the distance limitation in refrigerated rooms and spaces.
Section 1006.3.2: For buildings with one exit.
Section 1029.7: For increased limitation in assembly seating.
Section 3103.4: For temporary structures.
Section 3104.9: For pedestrian walkways.
b. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where sprinkler systems are permitted in accordance with Section 903.3.1.2.
c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
d. Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.1.
1017.2 Exterior egress balcony increase.
Exit access travel distances specified in Table 1017.2 shall be increased up to an additional 100 feet (30 480 mm) provided the last portion of the exit access leading to the exit occurs on an exterior egress balcony constructed in accordance with Section 1021. The length of such balcony shall be not less than the amount of the increase taken.