716.5.10 Swinging fire shutters.
Where fire shutters of the swinging type are installed in exterior openings, not less than one row in every three vertical rows shall be arranged to be readily opened from the outside, and shall be identified by distinguishing marks or letters not less than 6 inches (152.4 mm) high.
716.5.11 Rolling fire shutters.
Where fire shutters of the rolling type are installed, such shutters shall include approved automatic-closing devices.
716.6 Fire-protection-rated glazing.
Glazing in fire window assemblies shall be fire protection rated in accordance with this section and Table 716.6. Glazing in fire door assemblies shall comply with Section 716.5.8. Fire-protection-rated glazing in fire window assemblies shall be tested in accordance with and shall meet the acceptance criteria of NFPA 257 or UL 9. Fire-protection-rated glazing shall comply with NFPA 80. Openings in nonfire-resistance-rated exterior wall assemblies that require protection in accordance with Section 705.3, 705.8, 705.8.5 or 705.8.6 shall have a fire-protection rating of not less than 3/4 hour.
Type of Assembly | Required Wall Assembly Rating (hours) | Minimum Fire Window Assembly Rating (hours) | Fire-Rated Glazing Marking |
Type of Assembly | Required Wall Assembly Rating (hours) | Minimum Fire Window Assembly Rating (hours) | Fire-Rated Glazing Marking |
Interior walls: | NP
a | ||
Fire walls | All | NP
a | W-XXX
b |
Fire barriers | >1 1 | NP
a | W-XXX
b W-XXX b |
Incidental use areas (Section 707.3.7), Mixed occupancy separations (Section 707.3.9) | 1 | 3/4 | OH-45 or W-60 |
Fire partitions | 1 | 3/4 | OH-45 or W-60 |
Smoke barriers | 1 | 3/4 | OH-45 or W-60 |
Exterior walls | >1 1 | 1 1/2 3/4 | OH-90 or W-XXX
b OH-45 or W-60 |
Party wall | All | NP | Not Applicable |
NP = Not Permitted.
a. Not permitted except fire-resistance-rated glazing assemblies tested to ASTM E 119 or UL 263, as specified in Section 716.2.
b. XXX = The fire rating duration period in minutes, which shall be equal to the fire-resistance rating required for the wall assembly.
716.6.1 Testing under positive pressure.
NFPA 257 shall evaluate fire-protection-rated glazing under positive pressure. Within the first 10 minutes of a test, the pressure in the furnace shall be adjusted so not less than two-thirds of the test specimen is above the neutral pressure plane, and the neutral pressure plane shall be maintained at that height for the balance of the test.