509.1 General.
Incidental uses listed in Table 509 and located within single occupancy or mixed occupancy buildings shall comply with the provisions of this section. Incidental uses are ancillary functions associated with a given occupancy that generally pose a greater level of risk to that occupancy and are limited to those uses listed in Table 509.
Exception: Incidental uses within and serving a dwelling unit are not required to comply with this section.
Room or Area | Separation and/or Protection |
Room or Area | Separation and/or Protection |
Furnace room where any piece of equipment is over 350,000 Btu per hour input | 2 hour; or 1 hour and provide automatic sprinkler system
a |
Furnace room where any piece of equipment is 350,000 Btu per hour input or less, except in R-3 occupancy | 1 hour or provide automatic sprinkler system
a |
Rooms with a high pressure steam or water boiler that exceeds 350,000 Btu per hour input | 2 hour; or 1 hour and provide automatic fire-extinguishing system
a |
Rooms with a high pressure steam or water boiler that is 350,000 Btu per hour input or less | 1 hour or provide automatic sprinkler system
a |
Rooms that contain a low pressure steam or water boiler regardless of Btu per hour input | 1 hour or provide automatic sprinkler system
a, b |
Refrigerant machinery room | 1 hour or provide automatic sprinkler system |
Hydrogen fuel gas rooms, not classified as Group H | 2 hours in all occupancies |
Incinerator rooms | 2 hours and automatic sprinkler system |
Paint shops, not classified as Group H, located in occupancies other than Group F
| 2 hours; or 1 hour and provide automatic sprinkler system |
In Group E occupancies, laboratories and vocational shops not classified as Group H | 1 hour or provide automatic sprinkler system |
In Group I-2 occupancies, laboratories not classified as Group H | 1 hour and provide automatic sprinkler system |
In ambulatory care facilities, laboratories not classified as Group H | 1 hour or provide automatic sprinkler system |
Laundry rooms over 100 square feet | 1 hour or provide automatic sprinkler system |
In Group I-2, laundry rooms over 100 square feet | 1 hour |
Group I-3 cells and Group I-2 patient rooms equipped with padded surfaces | 1 hour |
In Group I-2, physical plant maintenance shops | 1 hour |
In ambulatory care facilities or Group I-2 occupancies, waste and linen collection rooms with containers that have an aggregate volume of 10 cubic feet or greater | 1 hour |
In other than ambulatory care facilities and Group I-2 occupancies, waste and linen collection rooms over 100 square feet | 1 hour or provide automatic sprinkler system |
In ambulatory care facilities or Group I-2 occupancies, storage rooms greater than 100 square feet | 1 hour |
Stationary storage battery systems having an energy capacity greater than the threshold quantity specified in Table 608.9.1.1 of the New York City Fire Code | 1 hour in group B, F, M, S and U occupancies; 2 hours in Group A, E, I and R occupancies |
Rooms containing fire pumps in non-high-rise buildings | 2 hours; or 1 hour and provide automatic sprinkler system throughout the building |
Rooms containing fire pumps in high-rise buildings | 2 hours |
For SI: 1 square foot = 0.0929 m
2
, 1 pound per square inch (psi) = 6.9 kPa, 1 British thermal unit (Btu) per hour = 0.293 watts, 1 horsepower = 746 watts, 1 gallon = 3.785 L, 1 cubic foot = 0.0283 m
3
.
a. Boilers servicing more than one dwelling unit in Multiple dwellings shall also comply with Section 65 of the New York State Multiple Dwelling Law.
c. For mechanical and/or electrical equipment rooms not identified in this table, see Section 508.1.
(Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023)
Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.