702.1 Above-ground sanitary drainage and vent pipe.
Above-ground soil, waste and vent pipe shall conform to one of the standards listed in Table 702.1.
Material | Standard |
Material | Standard |
Acrylonitrile butadiene styrene (ABS) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200) and DR 24 (PS 140); with a solid, cellular core or composite wall
a | ASTM D 2661; ASTM F 628; ASTM F 1488; CSA B181.1 |
Brass pipe | ASTM B 43 |
Cast-iron pipe | ASTM A 74; ASTM A 888; CISPI 301 |
Copper or copper-alloy pipe | ASTM B 42; ASTM B 302 |
Copper or copper-alloy tubing (Type K or L) | ASTM B 75; ASTM B 88; ASTM B 251 |
Ductile iron | AWWA C151 |
Galvanized steel pipe | ASTM A 53 |
Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200), and DR 24 (PS 140); with a solid, cellular core or composite wall
a | ASTM D 2665; ASTM F 891; ASTM F 1488; CSA B181.2 |
Polyvinyl chloride (PVC) plastic pipe with a 3.25-inch O.D. and a solid, cellular core or composite wall
a | ASTM D 2949; ASTM F 1488 |
Stainless steel drainage systems, Types 304 and 316L | ASME A112.3.1 |
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
702.2 Underground building sanitary drainage and vent pipe.
Underground building sanitary drainage and vent pipe shall conform to one of the standards listed in Table 702.2.
Material | Standard |
Cast-iron pipe | ASTM A 74; ASTM A 888; CISPI 301 |
Copper or copper alloy tubing (Type K or L) | ASTM B 75; ASTM B 88; ASTM B 251 |
Ductile iron | AWWA C151 |
Polyolefin pipe | ASTM F 1412; CSA B181.3 |
Polyvinyl chloride (PVC) plastic pipe in IPS diameters, including Schedule 40, DR 22 (PS 200), and DR 24 (PS 140); with a solid, cellular core or composite wall
a | ASTM D 2665; ASTM F 891; ASTM F 1488; CSA B181.2 |
Stainless steel drainage systems, Type 316L | ASME A112.3.1 |
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
702.3 Building drain pipe.
Material | Standard |
Material | Standard |
Cast-iron pipe | ASTM A 74; ASTM A 888; CISPI 301 |
Chlorinated polyvinyl chloride (CPVC) plastic a | ASTM F 437; ASTM F 438; ASTM F 439 |
Copper or copper-alloy tubing (Type K or L) | ASTM B 75; ASTM B 88; ASTM B 251 |
Ductile iron | AWWA C151 |
Galvanized steel pipe | ASTM A 53; ASTM A 123 |
Polyvinyl chloride (PVC) plastic pipe (Type DWV, SDR26, SDR35, SDR41, PS50 or PS100)
a | ASTM D 2665; ASTM D 3034; ASTM F 891; CSA B182.2; CSA B182.4; CSA B181.2 |
Stainless steel drainage systems, types 304 and 316L | ASME A112.3.1 |
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
702.4 Fittings.
Pipe fittings shall be approved for installation with the piping material installed and shall comply with the applicable standards listed in Table 702.4.
Material | Standard |
Material | Standard |
Acrylonitrile
butadiene styrene (ABS) plastic pipe in IPS diameters
a | ASTM D 2661; ASTM F 628; CSA B181.1 |
Acrylonotrile butadiene styrene (ABS) plastic pipe in sewer and drain diameters | ASTM D 2751 |
Brass | ASTM B 62 |
Cast iron | ASME B16.4; ASME B16.12; ASTM A 74; ASTM A 888; CISPI 301 |
Chlorinated polyvinyl chloride (CPVC) plastic a | ASTM F 437; ASTM F 438; ASTM F 439 |
Copper or copper alloy | ASME B16.15; ASME B16.18; ASME B16.22; ASME B16.23; ASME B16.26; ASME B16.29 |
Galvanized steel | ASTM A 153; ASME B16.3 |
Ductile iron | AWWA C110 |
Malleable iron | ASME B16.3 |
Polyethylene (PE) plastic pipe a | ASTM F 2306 / F 2306M |
Polyvinyl chloride (PVC) plastic in IPS diameters a | ASTM D 2665; ASTM F 1866 |
Polyvinyl chloride (PVC) plastic pipe in sewer and drain diameters
a | ASTM D 3034 |
Polyvinyl chloride (PVC) plastic pipe with a 3.25-inch O.D.
a | ASTM D 2949 |
Stainless steel drainage systems, Types 304 and 316L | ASME A112.3.1 |
For SI: 1 inch = 25.4 mm.
a. Limited to residential buildings five stories or less in height.
702.5 Temperature rating.
Where the waste water temperature will be greater than 140°F (60°C), the sanitary drainage piping material shall be rated for the highest temperature of the waste water.
702.6 Chemical waste system.
A chemical waste system shall be completely separated from the sanitary drainage system. The chemical waste shall be treated in accordance with Section 803.2 before discharging to the sanitary drainage system. Separate drainage systems for chemical wastes and vent pipes shall be constructed in accordance with Section 803.3.