5403.2 Quantities exceeding the maximum allowable quantity per control area.
The storage, handling and use of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC 5003.1 shall be in accordance with this chapter and FC Chapter 50.
5404.1 Indoor storage.
Indoor storage of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(2), shall be in accordance with FC 5001, 5003, 5004 and this chapter.
5404.1.1 Liquid-tight floor.
In addition to the provisions of FC 5004.12, floors in storage areas for corrosive liquids shall be of liquid-tight construction.
5404.2 Outdoor storage.
Outdoor storage of corrosive materials in amounts exceeding the maximum allowable quantity per control area indicated in FC Table 5003.1.1(4) shall be in accordance with FC 5001, 5003, 5004 and this chapter.
5404.2.1 Aboveground outdoor storage tanks.
Aboveground outdoor storage tanks exceeding an aggregate quantity of 1,000 gallons (3785 L) of corrosive liquids shall be provided with secondary containment in accordance with FC 5004.2.2.