5104.7 Storage in Group M occupancies.
Storage of Level 2 and 3 aerosol products in occupancies in Group M shall comply with the requirements of FC Table 5104.7. Retail display shall comply with the requirements of FC 5106.
Maximum Net Weight Per Floor (pounds) | |||
Floor | Nonsegregated storage a, b | Segregated storage | |
Storage cabinets b | Separated from retail area c | ||
Basement, cellar or other area below grade | Not permitted | Not permitted | Not permitted |
Ground floor | 2,500 | 5,000 | Note d |
Upper floors | 500 | 1,000 | Note d |
For SI: 1 pound = 0.454 kg, 1 square foot = 0.0929 m2.
a. The total aggregate quantity on display and in storage shall not exceed the maximum retail display quantity indicated in FC 5106.3.
b. Storage quantities indicated are the maximum allowed in any 50,000-square-foot area.
c. The storage area shall be separated from the retail area with a 1-hour fire-resistance-rated assembly.
d. See FC Table 5104.3.2.
5105.1 General.
The outdoor storage of Level 2 and 3 aerosol products, including storage in temporary storage trailers, shall be separated from exposures in accordance with FC Table 5105.1.
Exposure | Minimum Distance from Aerosol Storage (feet) a |
Public streets or private roads | 20 |
Buildings | 50 |
Exit discharge to a public street or private road | 50 |
Lot lines | 20 |
Other outdoor hazardous material storage | 50 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The minimum separation distance indicated is not required where exterior walls having a 2-hour fire-resistance rating without penetrations separate the storage from the exposure. The walls shall extend not less than 30 inches above and to the sides of Level 2 and 3 aerosol products.
5106.1 General.
This section shall apply to the retail display of Level 2 and 3 aerosol products.