§ 51.41 PROVISION FOR CUT-OFF VALVE.
   (A)   Any person desiring to connect to a water supply and distribution system owned and/or operated by HRW shall be required to install a cut-off valve of a minimum size of 3/4 of an inch onto the service line running from the meter box to the consumer's premises. This cut-off valve shall be located within 12 inches of the connection of the customer's service line to the meter box. A diagram showing a typical installation of such cut-off valve is attached to the Ordinance passed 11-16-2020, and made part of this section by reference.
   (B)   This section shall be enforceable in addition to the minimum requirements of the North Carolina State Building Code regarding plumbing and placement of cut-off valves.
(Ord. passed 6-30-2015; Ord. passed 7-16-2018; Ord. passed 6-15-2020; Ord. passed 11-16-2020)