Loading...
18-29-1109.1 Equivalent roof area.
   Where there is a continuous or semi-continuous discharge into the building storm drain or building storm sewer, such as from a pump, ejector, air conditioning plant or similar device, each gallon per minute (L/m) of such discharge shall be computed as being equivalent to 24 square feet (2.25 m 2 ) of roof area. (See Table 18-29-1108.1)
18-29-1110 Controlled Flow Roof Drain Systems.
18-29-1110.1 General.
   The roof of a structure shall be designed for the storage of water where the storm drainage system is engineered for controlled flow. The controlled flow roof drain system shall be an engineered system in accordance with this section and the design, submittal, approval, inspection and testing requirements of Section 18-29-1105.4. In lieu of the conventional downspout requirements of Section 18-29-1106, controlled flow roof drainage may be used. The water of a 25 year frequency shall not be stored on the roof for more than 24 hours. The water depth on flat roofs shall not exceed 3 inches (75 mm) during the above storm and 3 inches (75 mm) average depth on sloped roofs not exceeding 6 inches (32 mm) rise or depth of slope.
18-29-1110.1.1 Design.
   The flow rate (gpm) shall be determined by the use of Chart 18-29-1110.1.1 A for flat roofs and Chart 18-29-1110.1.1 B for slope roofs. The size of the vertical pipe and horizontal pipe shall be determined by the use of Tables 18-29-1110.1.1 C for vertical pipe and Table 18-29-1110.1.1 D for horizontal pipe and in no case shall be less than 3 inches (75 mm). The capacity rating (gpm) of any controlled flow downspout, branch or storm drain shall be converted to an equivalent square foot area by multiplying the gallons per minute (gpm) by 24 (24 square feet of roof area equals 1 gpm) before connecting to any combined house drain or house sewer, and add this value to the total drained area of Section 18-29-1106 of this chapter. Downspouts that are offset at 90 degrees shall be full size to the storm drain or sewer or combined drain or sewer.
Chart 18-29-1110.1.1 A and
Chart 18-29-1110.1.1 B
Table 18-29-1110.1.1
Diameter of Downspout
Max. Horizontal Projected Roof Area Square Feet
Diameter of Downspout
Max. Horizontal Projected Roof Area Square Feet
2"
720
2 1/2"
1,300
3"
2,150
4"
4,600
5"
8,300
6"
13,000
8"
29,000
10"
52,000
12"
83,000
13"
155,000
 
Table 18-29-1110.1.1C
Vertical
Diameter of Downspout
Max. Vertical Projected Roof Area Square Feet
Diameter of Downspout
Max. Vertical Projected Roof Area Square Feet
3"
88
4"
190
5"
345
6"
560
8"
1,210
10"
2,185
12"
3,570
15"
6,450
 
Table 18-29-1110.1.1D
Horizontal
Maximum Controlled Flow in GPM
Pipe Diameter in Inches
Slope in Inches in gpm
1/2
1/4
1/8
1/16
Maximum Controlled Flow in GPM
Pipe Diameter in Inches
Slope in Inches in gpm
1/2
1/4
1/8
1/16
3"
72
51
N.P.
N.P.
4"
156
110
78
N.P.
5"
282
200
140
N.P.
6"
460
325
230
N.P.
8"
990
700
495
N.P.
10"
1,795
1,265
895
630
12"
2,065
1,460
1,030
15"
2,650
1,870
 
18-29-1110.2 Control devices.
   The control devices shall be installed so that the rate of discharge of water per minute shall not exceed the values for continuous flow as indicated in Section 18-29-1110.1.1. A scupper drain or drains shall be placed in the parapet wall at an invert elevation 1/2 inch (12 mm) above the maximum designed head. The scupper shall have a cross sectional area equal to that as required for conventional roof drainage. Control of runoff from roofs shall be by pre-calibrated tamper proof weirs; no valves or mechanical devices shall be permitted.
   Exception: Scuppers are not permitted in fire walls provided in accordance with Chapter 15-8 or 14B-7, as applicable.
(Amend Coun. J. 4-10-19, p. 100029, Art. XVI, § 13)
18-29-1110.3 Installation.
   Runoff control shall be by control devices. Control devices shall be protected by strainers.
18-29-1110.4 Minimum number of roof drains.
   Not less than two drains shall be installed in roof areas 10,000 square feet (930 m 2 ) or less and not less than four roof drains shall be installed in roofs over 10,000 square feet (930 m 2 ) in area.
18-29-1111 Sumps.
18-29-1111.1 Subsoil drains.
   Subsoil drains shall be open-jointed, horizontally spill or perforated pipe conforming to one of the standards listed in Table 18-29-1102.5. Such drains shall not be less than 4 inches (100 mm) in diameter. Where the building is subject to backwater, the subsoil drain shall be protected by an accessibly located backwater valve. Subsoil drains shall discharge to a trapped sump or approved location above ground. The subsoil sump shall not be required to have either a gastight cover or a vent. Access for the purpose of cleaning and removing obstructions in subsoil drains shall be provided at every change of direction.
Loading...