Listed and labeled self-contained, factory-built equipment and appliances shall be tested in accordance with the applicable standards specified in Table 18-28-1101.2. Such equipment and appliances shall be deemed to meet the design, manufacture and factory test requirements of this chapter if installed in accordance with their listing and the manufacturer's instructions.
Equipment | Standards |
Refrigeration fittings, including press-connect, flared and threaded | UL 109 and UL 207 |
Air-conditioning equipment | UL 1995 or UL/CSA 60335-2-40 |
Packaged terminal air conditioners and heat pumps | UL 484 or UL/CSA 60335-2-40 |
Dehumidifiers | UL 1995 or UL/CSA 60335-2-40 |
Unit coolers | UL 474 or UL/CSA 60335-2-40 |
Commercial refrigerators, freezers, beverage coolers and walk-in coolers | UL 412 or UL/CSA 60335-2-40 |
Refrigerating units and walk-in coolers | UL 427 or UL/CSA 60335-2-40 |
Refrigerant-containing components and accessories | UL 207 |
(Amend Coun. J. 9-14-21, p. 35949, Art. XI, § 1)